7
Linearis N+
3.4
Performance data
•
Protection class: IP65 (optional IP 66, IP 67)
•
Motor: 230V ±10%, 50/60Hz ±5%, 100% ED (Standard)
» Special voltage/-frequency see nameplate (Option)
» Insulation class E acc. DIN EN 60034-1
•
Motor: 24 V DC (Option) ±20%, ED S3 50%
» Insulation class E acc. DIN EN 60034-1
•
Connection: 3 cable glands M16x1.5 (Customer provided)
•
Path cut-off: Changeover switch (Opener/Closer)
» Switching capacity max. 10(3)A, 250V AC
•
Ambient temperature
» -15 °C up to +60 °C (optional -30 °C...+80 °C)
•
Installation position: Arbitrary
•
Potentiometer (Option)
» Recommended wiper current: 0,2 μA
» Capacity at +70 °C: 0,5 W
•
Travel: 150 mm, 300 mm
3.5
Expected lifespan and intended disposal
ARIS actuators have an expected lifespan of several years, depending on their utilization and application. No longer usable actu-
ators must not be dismantled as a whole, but seperately recycled in parts divided by their materials. Non-recyclable components
must be disposed according to national disposal regulations.
4.
Actuator setup for operation
4.1
Transport and (temporary) storage
Use the factory packaging for transport to the installation point. Replace a damaged original packaging by a new solid packaging.
Suspended load
Improper use of transportation (ground conveyer, overhead crane, tools, lifting means etc.) can cause crushes and other injuries.
Required behaviour:
•
Use transportation properly;
•
DO NOT step or stand under suspended loads;
•
Actuators with attached valves: Attach lifting gear only on the valve and NEVER on the actuator;
•
Do not use ARIS actuators as a climbing or support aid;
Damage by wrong storage
•
Store in well-ventilated rooms;
•
Protection against possible ground humidity (shelf storage).
WARNING
ADVICE
!
Содержание Linearis N+
Страница 19: ...Manual for ARIS Microprocessor Controller PMR Nano PMRN1429EN01 Stellantriebe ...