DMX-CAN Manual
page 18
rev 1.6
A.
Serial Communication Port Number. This is a drop down combo box which
has selection of serial port from COM1 to COM15.
B.
9600 baud rate is the default communication baud rate that is used. If you
have set your DMX-CAN module to operate at a different baud rate, select the
correct baud rate here.
C.
Device name is used for RS-485 communication and to distinguish many
devices on the RS-485 network.
D.
Search button is used to search for any DMX-CAN module connected to an
available serial communication port. Search looks for DMX-CAN from
COM1 to COM15 using the device name.
E.
Search All button is used to search for all DMX-CAN modules connected to
the available serial communication port. This button should be used when
more than one DMX-CAN are connected on a multi-drop RS-485 bus. Note
that the DMX-CAN must be configured to use RS-485 communication.
F.
Open connection uses the selected COM port and the device name to open
communication with the DMX-CAN module.
G.
Close the application program.
When connecting for the first time, we recommend that search is done to find out the
COM port number where the DMX-CAN is connected.
If search cannot find the DMX-CAN device or open connection does not find the DMX-
CAN, check the following:
1)
Check power supply to DMX-CAN. Recommended power is from 12VDC to
35VDC.
2)
Check communication wiring. If using RS-232, TXD from DMX-CAN
should be connected to RXD of the serial port and RXD from DMX-CAN
should be connected to TXD of serial port. If using RS-485, make sure that
the 485+ from DMX-CAN is connected to 485+ of the master and 485- from
DMX-CAN is connected to 485- of the master.
3)
Confirm that the device name is set correctly. Default factory device name
setting is “01”. If this name has been changed and stored to flash, enter the
new name.