Room temperature
sensor malfunction
Indoor coil
temperature sensor
malfunction
Anti-frozen
protection at
cooling
Poor heating(the
refrigerant charge is
deficient)
Extra high temperature
protection at heating
mode
Check if the connection loosing; if not, replace the
sensor. Check if 4-air outlet are open(at least 2 should
be open).
Check if the connection to PCB loosing; or if copper
sensor comes out; if not, replace the senser.
Poor cooling (the
refrigerant charge is
deficient, or the airflow
is insufficient or the
outdoor exhuast air
vents are obstructed )
1. Compressor is running(no wiring disconnected).
2. Check if ceiling panel installed correctly, ensure no air
flow shorted.
3. Gas leakage happened, repairing is needed.
1. Compressor is running(no wiring disconnected);
2. Check if ceiling panel installed correctly, ensure no air
flow shorted.
3. Gas leakage happened, repairing is needed.
1. Filter too dirty? Clean the filter.
2. Unit is running at a very high outside
temperature(higher than 20° C)? Suggest to open
window instead of running air conditioner heating.
3. Four direction air outlet must have at least 2 open.
4. Indoor fan running at normal speed? If not, check the
motor.
1. Filter too dirty? Clean the filter.
2. Unit is running at a very low outside
temperature(lower than 18° C)? Suggest to open
window instead of running air conditioner cooling.
3. Four direction air outlet must have at least 2 open.
4. Indoor fan running at normal speed? If not, check the
motor.
E1
E2
E3
E5
E4
E6
Error Code
Problem
Solution
Содержание KAC 25
Страница 12: ...CN 12 04 383mm 958mm 720mm 364mm 560mm 479mm ...
Страница 16: ...CN 16 08 09 ...
Страница 25: ...Make A Difference 卓 尔 不 凡 CN 11 0 电路接线图 25 KAC 33 接线图 ...
Страница 26: ...CN 26 KAC 25 接线图 ...
Страница 28: ...CN 28 上风管 底板 16 17 18 21 19 22 20 23 下风管 显示板 面板固定板 面板 百叶 回风面罩 16 17 18 19 20 21 22 23 ...
Страница 56: ...EN KAC 25 56 ...