1100-2184 Rev 0
29
c. Hold the magnet wand to Magnetic Switch A (marked with a single dot “
•
” on
the AT-G-ALERT) for 60 seconds. The device should beep at the end of 60
seconds to indicate reset.
d. Remove the magnet wand and cycle power. The AT-G-ALERT will have
reverted to default settings including default Modbus ID 1.
e. Specify a unique ID for the AT-G-ALERT– this can a number 2 through 16,
inclusive.
f. Tap
Set Unit ID
to apply this ID.
g. Repeat the above steps for each device. Keep track of the assigned IDs and
install according to the floorplan spreadsheet.
Figure 31 - Set Unit ID