1100-2184 Rev 0
13
Network Creating Notes:
•
To mark devices to be on the same floor, those devices must have the same
floor name (capitalisation matters). The AT-G-ALERT-C will display a new
“floor” tile for each unique name appearing in the floorplan spreadsheet, up to
16 distinct values.
•
The floor and room cells can be named with any combination of up to eight
digits of letters and/or numbers.
•
It is possible to hardwire up to 15 devices to the controller’s Modbus RTU
port. To indicate these in the floorplan, fill in the cells at the bottom of the
spreadsheet (rows with IP marked “Direct”).
•
Each Gateway’s IP Address must be unique. If only one gateway is used, its
IP address should be 192.168.0.1. The IP address for subsequent gateways
would be 192.168.0.2, 192.168.0.3, etc.
•
The 7th gateway, if used, has a limit of 10 devices. All other gateways have a
limit of 15 devices.
Figure 8 –Example of a Small Network