1100-2184 Rev 0
20
Note:
Take care to ensure proper wiring for intended function: normally open and /
or normally closed.
3.6 Battery for Persistent Memory
When 24V DC power is lost to the AT-G-ALERT-C, a backup battery is used to save
the current state of the system, including the event history and the date and time
settings.
This
MUST
be activated by pulling out the plastic spacer separating the battery from its
contacts. This plastic spacer is labelled with “
Pull out to activate battery
”.
If this step was skipped, and a system state loss occurs after fully
commissioning, re-upload the floorplan from the USB and select
Commission All
from the settings menu to reconnect all devices.
3.7 Connecting Ethernet Gateways
Connect the Ethernet output from the controller to the gateway(s).
Note:
If multiple gateways are in use, their Ethernet ports may be daisy chained or
an optional Ethernet switch can be used to connect all gateways and the
controller onto the same local subnetwork.
Figure 18 - Wiring Relays