1100-2184 Rev 0
19
3.4 Hardware Installation
Mount the AT-G-ALERT-C in an accessible location for viewing alerts and responding to
alarm conditions.
Environment: place the AT-G-ALERT-C in an indoor setting free from the risk
of exposure to water, high humidity or any hazardous conditions.
Accessibility: ensure that the AT-G-ALERT-C’s touch screen is readily
accessible for viewing alerts and responding to alarm conditions.
Connect the controller to a 24VDC supply capable of at least 1 Amp output.
WARNING
: Do not apply power until all wiring is in place.
Near to the 24V DC is a terminal block for direct Modbus RTU connections.
This is to be used for troubleshooting or very small direct-connected networks with less
than 15 units. A typical large floorplan should be divided into segments connecting via
Gateways, as described earlier.
3.5 Connecting Relays: Alarm, Fault
If used, connect the relay output(s) to equipment that will be triggered by each relay.
Figure 17 - Modbus Wiring