Set Pre-Bleed/Bleed Lockout Screen
Allows the user to set pre-bleed and bleed lockout times in hours.
PRE-BLEED SET: [0]
Options: Value in the range of 0 to 9.9 hours.
Use arrow keys to cycle these selections.
For a value of 0 pre-bleed is inactive.
Pre-bleed is a function used to reduce the conductivity of the
system before each biocide dose. When active, pre-bleed will trigger
responses at 87.5% of the conductivity set point.
BLEED LOCKOUT: [0]
Options: Value in the range of 0 to 9.9 hours.
Use arrow keys to cycle these selections.
For a value of 0 pre-bleed is inactive.
Bleed lockout is a function used to retain the biocide that is being
dosed for a set time. When active, pre-bleed will trigger lockout
responses to an automatic override at 112.5% of the conductivity
set point.
Set Seven Day Timers Screen
Allows the user to configure the biocide dosing timer to control the
days of the week that it will dose.
T1 Mode: [Mon+Wed+Fri]
Options:
Any Day
Mon-Fri
Mon+Wed+Fri
ALL
OFF.
T1 ON: [0]
Options: (dosing start times) 24 hr timer.
Use arrow keys to cycle these selections.
T1 Dur: [0]
Options: (dose duration) In the range of 0 to 9.9 hours.
Use arrow keys to cycle these selections.
Warning defaults: Time ON greater than 2 hrs. The controller will
issue a warning when this value is exceeded.
At the completion of the setting for the first timer T1, the screen will
cycle to the remaining 5 timers, T2, T3, T4, T5, T6. The user may
follow the preceding steps to activate one or more of those additional
timers.