16
Set Alarm Screen - Name and Phone
Allows the user to enter up to three names and contact phone numbers
to receive notification of system alarms via mobile phone sms alerts.
Only available when a Communications Kit is fitted to
the controller
Options: (three phone numbers)
PH1/PH2/PH3 Use the arrow keys to cycle through these
selections.
Press ENT to place the cursor on the NAME field and use arrow
keys to select characters. Press ENT to select and move the cursor
to the next character. Pressing ENT a second time will move the
cursor to the NUM field. The same process applies for entering the
telephone number, the arrow keys cycle numbers 0 through 9 and
ENT to move to the next number.
Set Conductivity Screen
Refer to Table 1. Adjacent.
Allows the user to set the conductivity options for the controller.
mS/cm is a read only value generated by the controller. It conveys
the actual value measured by the conductivity sensor, in millisiemens
per centimetre.
Models
Conductivity
CT
Series
C [x]
Series
S
Series
T
Series
A & P
Series
Options
Available
Above
Above
Above/
Below
Above/
Below
Below
Default Mode
Above
Above
Above
Above
Below
Table 1.
3ET!LARMS
0(
.!-%
.5-
3ET#ONDUCTIVITY
M3CM3%4
-/$%/&&
!,-/&&,/#+.!
SET: [value from Table 1]
Options: Value range 00.20 to
10.00.
Use arrow keys to cycle these
selections.
MODE:
[FLOW)
Options: OFF/FLOW/
CON.
Use arrow keys to cycle these
selections.
ALM: [+/-]
Options:
+ (alarm if above specified value)
- (alarm if below specified value)
+/- (alarm if outside specified
range)
OFF (Alarm disabled)
Use arrow keys to cycle these
selections.
When the cursor is on one of the alarm modes press ENT to change
the numerical values associated with that alarm. Select from the
values of 0.1, 0.2, 0.4, 0.8, 1.0, 1.5 and 2.0. These values are the
range from the set point that will trigger an alarm. Press the ENT
again to move to the next set conductivity item.
LOCK:
is not applicable to Conductivity.
The controller will alert the user after five minutes if actual value
deviates greatly from the set point value. This aids the prevention
of false alarms.
2
System Configuration
2
System Configuration