27
2
System Configuration
2
System Configuration
Biocide-B
RL=OFF
DUTY=100% MODE=T&FLO
WK1=BIO-B WK2=BIO-B
WK3=BIO-B WK4=BIO-B
Seven Day Timer Config Read Screen
This screen displays the biocide pump duty and mode of operation.
RL (relay): OFF/ON
DUTY: the current value set MODE:T&FLO/TIMER
WK1: BIO-A/B
WK2: BIO-A/B
WK3: BIO-A/B
WK4: BIO-A/B
For descriptions and information on setting these items, refer to the
section Set Biocide Duty/Mode Screen
Pre-Bleed/Bleed Lockout Read Screen
This screen displays information concerning the status of pre-bleed
and bleed lockout times for the system.
PB:
ON/OFF
BLO:
ON/OFF
PRE-BLEED SET: Setting in hours
BLEED LOCKOUT: Setting in hours
For descriptions and information on setting these items, refer to the
section Set Pre-bleed and Bleed Lockout Screen.
Seven Day Timer Read Screen
This screen displays the biocide program information. If more than
one timer is set the screen will cycle through all programs.
TMRS EN: Timers enabled (1, 2, 3, 4, 5, 6)
T(x): Each of the enabled timers will flash on this line showing their
frequencies.
The following two values are associated with the timer indicated in
the line above.
ON: The start time for the timer indicated
DUR: The duration of dosing for the timer indicator
For descriptions and information on setting these items, refer to the
section Set Biocide Timers screen.
Disinfection Read Screen
This screen displays information about the disinfection routines for
the system.
ON/OFF:
Disinfection ON or OFF
DAY:
The day selected for disinfection
START:
Start time
DUR:
Dosing duration in hours
SET:
ORP control set point for disinfection
The WK and NXT fields are only visible if a disinfection program is
set.
WK:
The interval between cycles in weeks
NXT:
Date next disinfection will occur.
For descriptions and information on setting these items, refer to the
section Set Disinfection Screen.
$ISINFECTION
/&&
$!93AT34!24
$52HRS3%4M6
7+.84
Biocide-B TIMERS
TMRS EN= 1,2,3,4,5,6
T3 = Mon+Wed+Fri
ON=03:00 Dur=3.3hrs
Biocide-B BLEED
PB=OFF BLO=OFF
PRE-BLEED SET=9.9hrs
BLEED LOCKOUT=9.9hrs