RMC

 

Commissioning 

 

The  Rack  Multi  Control  is  developed  for  smooth  and  user  friendly  configuration.  When 
delivered from the factory the RMC is configured to monitor one temperature and to generate 
an alarm on channel 1 if the temperature reaches the high limit value of 60 degrees Celsius. 
 
 
When power is connected the RMC backlight activates and 
the latest firmware  is displayed. The backlight  can also  be 
activated  be  pressing  any  of  the  navigation  buttons  and 
remains on for about 5 seconds. 
 
 
When  the  code  lock  accessory  is  used  in  conjunction  with  the  Emka  swing  handle  the 
backlight turns on when the door unlocks and turns off when locked. 
 
 
Next a lamp test is performed to insure their functionality. All channel indicators light up, first 
green then red. After a few seconds the temperature on sensor one is displayed. 
 
 
When the sensor is installed in the wrong manner the RMC 
will  display 

“Temp  sensor  error!”

  If  there  is  only  one 

temperature  sensor  connected,  it  must  be  installed  on 
analogue Input 1. 
 
 
The 8 digital und 4 analogue inputs are shown by the 8 alarm channels. When an alarm is 
raised, the corresponding visual alarm indicator lamp starts flashing red, the internal buzzer 
goes off and the display lists the event. The alarm is acknowledged by pressing any of the 
navigation  buttons.  The  buzzer  stops  and  the  corresponding  alarm  lamp  changes  from 
flashing red to steady red if the fault signal remains or extinguishes when the fault signal is 
resolved. 
 
 
 
 
 
 
 

Depending on the configuration, the 3 

potential-free outputs

 can actuate a fan can be 

activated  via  an  output  relay  and  an  alarm  message  is  send  via  an  Email  and/or  a 
mobile text message (optional GSM modem necessary) or a SNMP Trap. Also, one of 
8 digital inputs can be configured to  monitor the status of the fan and displays it  via 
the associated green lamp. 

 
 
 
 
 
 

Содержание 901-0101

Страница 1: ...APS Rack Multi Control RMC Manual...

Страница 2: ...Operation 7 Factory settings 8 Network installation 8 Graphic User Interface 9 Set time and date 9 Open the door 10 Alarm reset 10 Settings 10 Support 10 Power outputs 10 Settings 11 Alarm Status cha...

Страница 3: ...19 Rack and requires one rack unit space The RMC has an internal power unit and connects to a 230 VAC outlet It is recommended to have the RMC connected to an UPS Wiring diagram 1 2 3 4 5 6 7 8 9 10...

Страница 4: ...s condition as ON Choose normally closed when this corresponds to the standard condition Analogue Inputs The 4 analogue inputs are connected as follows Input 1 2 and 3 are for temperature sensors The...

Страница 5: ...to the code lock interface Important If the Code Lock Unit for Emka 2100 accessory is in use do not connect pins 29 and 30 since the Emka systems has its own power supply Power Relays The 3 power rela...

Страница 6: ...4 RS232 Front Interface 2 Display 5 Link Active LED 3 Navigation buttons Back side 1 Modem Interface RS232 5 Analogue Inputs 2 Keypad Interface Emka 2100 6 Alarm and Door Output 3 Ethernet Port 7 Out...

Страница 7: ...s displayed When the sensor is installed in the wrong manner the RMC will display Temp sensor error If there is only one temperature sensor connected it must be installed on analogue Input 1 The 8 dig...

Страница 8: ...is necessary to set an IP address and Subnet mask on the PC used for configuration The IP address on the RMC is set by using the navigation buttons on the device itself Use the button Down and scroll...

Страница 9: ...vent In case of a reboot the list of events is erased and RMC Reboot appears Set time and date In consideration of the environment and to avoid unnecessary maintenance the RMC has a calendar clock wit...

Страница 10: ...ng in red both on the RMC and on the main web page By pressing any of the front panel buttons or by clicking this button Alarm reset on the PC screen the alarm will be acknowledged Settings The button...

Страница 11: ...or lamp flashing even if the alarm condition no longer remains This makes it possible to observe intermittent error conditions If Alarm auto ack is selected the channel is automatically reset when the...

Страница 12: ...ol by temperature sensor 2 or manual control on off for the basic setting of the relay after a reboot Output 3 Select Heating if temp 1 low for temperature control by temperature sensor 1 Cooling if T...

Страница 13: ...edge Passwords Lock codes These controls access to all web pages The factory settings shown should be changed The Lock code temporary controls the code to be entered on the keypad to open the door The...

Страница 14: ...rn to the main page GSM Modem In order for the RMC to send notifications by text messages a GSM modem needs to be connected to the RS232 Interface GSM modem is an optional accessory The RMC confirms t...

Страница 15: ...Status for the three potential free outputs Can also be set on or off by the NMS rmcTrapMessage When an alarm trap is sent this object holds the alarm text string which is appended to the trap In the...

Страница 16: ...0101 RMC Rack Multi Control 832 700 902 GSM Modem xmodus inkl 832 700 910 DIN Assembly clip to Modem 901 0120 Temperature Sensor RMC 0 2 m 901 0121 Temperature Sensor RMC 3 0 m 901 0103 Smoke Detecto...

Отзывы: