12
RMC
Outputs:
The potential-free outputs can be configured to correspond to
specific alarms. The name given on the virtual button is also
shown on the graphical user interface.
Output 1
Select
“Cooling if Temp 1 high”
for temperature control by temperature sensor 1 or
"manual control on / off"
for the basic setting of the relay after a reboot.
Output 2
Select
“Cooling Temp 1 limit 2”
for temperature control by temperature sensor 1 when an
additional fan is required,
“Cooling if Temp 2 high”
for temperature control by temperature
sensor 2, or
"manual control on / off"
for the basic setting of the relay after a reboot.
Output 3
Select
“Heating if temp 1 low”
for temperature control by temperature sensor 1,
“Cooling if
Temp 3 high"
for temperature control by temperature sensor 3,
“On if analog 4 high/low”
for a humidity measurement controlled by humidity sensor 4 or
“manual control on / off”
for
the basic setting of the relay after a reboot.
Limit values:
The limit settings control the 3 potential-free outputs.
“Limit Value output 1, 2, 3”
defines the value at
which the potential-free outputs are activate when
the function is selected configured in
“Power
Outputs”
.
The following 8 values define the limit at which an
alarm is raised.