Settings 

 
The monitoring functions of the RMC can be configured 

via the menu

 “Settings”

 

 
Return to the main menu by pressing the "Back ". 

 

 

Alarm & Status channels: 

The 8 alarm channels can be freely assigned by mouse click. When  
delivered from the factory channel 1 is already configured for  
temperature monitoring.  
 
 

Signal source 

The monitoring function of the inputs can be set per signal source or input signal. e.g. 

"Temp 

1 too high" 

alarm is triggered when the temperature exceeds the set limit.  

 

Function 

Controls  whether  the  channel  should  act  as  alarm  or  status  indicator.  When  an  alarm  is 
raised, the channel indicator lamp starts flashing red. A memory function keeps the indicator 
lamp  flashing  even  if  the  alarm  condition  no  longer  remains.  This  makes  it  possible  to 
observe  intermittent  error  conditions.  If 

"Alarm  auto  ack"

  is  selected,  the  channel  is 

automatically  reset  when  the  alarm  condition  returns  to  normal. 

"Alarm  ack.  +  Trap  "

also 

sends an SNMP message. 
 

Local Alarm 

Selects what local action should be taken when an alarm occurs. Options are 

"Beeper",

 

"Alarm relay"

 (output relay for horn)

 

or 

“Beeper and relay"

 

Type of contact 

Selects whether the digital input is 

“normally open”

 

or 

“normally closed”.

 

 

Output action on Alarm 

Select  between 

“no  action”,  “Open  Door”, 

(the 

door lock is released) 

“output off" 

(the potential-free 

outputs are disconnected. In case a smoke detection 
is  in  the  rack,  any  active  fan  can  be  turned  off  or 

“Door and outputs”

.  

 

Alarm text 

Defines the text presented on the event list, in Email 
text  message  and  SNMP  traps.  This  text  is  freely 
selectable 

Содержание 901-0101

Страница 1: ...APS Rack Multi Control RMC Manual...

Страница 2: ...Operation 7 Factory settings 8 Network installation 8 Graphic User Interface 9 Set time and date 9 Open the door 10 Alarm reset 10 Settings 10 Support 10 Power outputs 10 Settings 11 Alarm Status cha...

Страница 3: ...19 Rack and requires one rack unit space The RMC has an internal power unit and connects to a 230 VAC outlet It is recommended to have the RMC connected to an UPS Wiring diagram 1 2 3 4 5 6 7 8 9 10...

Страница 4: ...s condition as ON Choose normally closed when this corresponds to the standard condition Analogue Inputs The 4 analogue inputs are connected as follows Input 1 2 and 3 are for temperature sensors The...

Страница 5: ...to the code lock interface Important If the Code Lock Unit for Emka 2100 accessory is in use do not connect pins 29 and 30 since the Emka systems has its own power supply Power Relays The 3 power rela...

Страница 6: ...4 RS232 Front Interface 2 Display 5 Link Active LED 3 Navigation buttons Back side 1 Modem Interface RS232 5 Analogue Inputs 2 Keypad Interface Emka 2100 6 Alarm and Door Output 3 Ethernet Port 7 Out...

Страница 7: ...s displayed When the sensor is installed in the wrong manner the RMC will display Temp sensor error If there is only one temperature sensor connected it must be installed on analogue Input 1 The 8 dig...

Страница 8: ...is necessary to set an IP address and Subnet mask on the PC used for configuration The IP address on the RMC is set by using the navigation buttons on the device itself Use the button Down and scroll...

Страница 9: ...vent In case of a reboot the list of events is erased and RMC Reboot appears Set time and date In consideration of the environment and to avoid unnecessary maintenance the RMC has a calendar clock wit...

Страница 10: ...ng in red both on the RMC and on the main web page By pressing any of the front panel buttons or by clicking this button Alarm reset on the PC screen the alarm will be acknowledged Settings The button...

Страница 11: ...or lamp flashing even if the alarm condition no longer remains This makes it possible to observe intermittent error conditions If Alarm auto ack is selected the channel is automatically reset when the...

Страница 12: ...ol by temperature sensor 2 or manual control on off for the basic setting of the relay after a reboot Output 3 Select Heating if temp 1 low for temperature control by temperature sensor 1 Cooling if T...

Страница 13: ...edge Passwords Lock codes These controls access to all web pages The factory settings shown should be changed The Lock code temporary controls the code to be entered on the keypad to open the door The...

Страница 14: ...rn to the main page GSM Modem In order for the RMC to send notifications by text messages a GSM modem needs to be connected to the RS232 Interface GSM modem is an optional accessory The RMC confirms t...

Страница 15: ...Status for the three potential free outputs Can also be set on or off by the NMS rmcTrapMessage When an alarm trap is sent this object holds the alarm text string which is appended to the trap In the...

Страница 16: ...0101 RMC Rack Multi Control 832 700 902 GSM Modem xmodus inkl 832 700 910 DIN Assembly clip to Modem 901 0120 Temperature Sensor RMC 0 2 m 901 0121 Temperature Sensor RMC 3 0 m 901 0103 Smoke Detecto...

Отзывы: