49
code HC0100.00GB ed.A-1509
HY
AQUAPUMP HYBRID
HYBRID HEATER
Parameters of CPU-SMART PCB version 7.01.xx
PARAMETER
HY434/534
DESCRIPTION
H14
%
100
PWM2 minimum value: 0÷100
H15
%
100
PWM2 maximum value: 0÷100
H16
2
2=circulator modulation proportional to FAN (do not change)
H17
1
0=PWM (Y1) or 0/10V (Y2) output according to "direct" logic;
1=PWM (Y1) or 0/10V (Y2) output according to "reverse" logic
H18
V
4
Y2 output voltage in conditioning mode
H19
°C
35
Reading of NTC1 to which the minimum value of Y2 output corresponds
H20
°C
60
Reading of NTC1 to which the maximum value of Y2 output corresponds
NTC2 control - not used
S2
1
0=NTC2 disabled; 1=NTC2 enabled
ST2
°C
5.0
NTC2 setpoint: -10÷90
P2
°C
2.0
ST2 hysteresis: 0÷40
XD2
40
Neutral area, proportional modulation band divided by one hundred: 4 ÷100
TN2
sec
5
Integration time: 1÷255
ANTIFREEZE control - active with D8=1
STA
°C
2.0
Antifreeze setpoint: -10÷+20
PA
°C
1.0
Antifreeze setpoint hysteresis: 0÷10
FUMES TEMPERATURE control - active with D5=1
H41
°C
5
Fumes temperature (NTC3); neutral band from 1÷50
H42
sec
5
Run time for fumes control cycle (15=30 seconds): 0÷255
H43
°C
95
Fumes temperature at maximum capacity (Tmax with PT%=100): 0÷140
H44
°C
85
Fumes temperature at medium capacity (Tmed with PT%=50): 0÷140
H45
°C
75
Fumes temperature at minimum capacity (Tmin with PT%=0): 0÷140
H46
0
Fumes temperature operation: 0=modulation only - 1=burner OFF
TH3
°C
103
Temperature upper limit (autoreset if NTC3<TH3): 0÷140
Hydraulic circuit WATER PRESSURE control
S5
3
Pressure probe B2 output enabling: 0=disabled; 1=enabled as ON/OFF input;
2=enabled as analogue input without fault F83 autoreset; 3=enabled as
analogue input with fault F83 autoreset
ST5
bar
0.70
B2 setpoint: 0÷9.99
P5
bar
0.30
ST5 hysteresis: 0÷9.99
XA5
V
1.18
B2 pressure probe signal input minimum voltage: 0÷9.99
XB5
V
2.72
B2 pressure probe signal input maximum voltage: 0÷9.99
YA5
bar
0.10
Pressure matching the B2 probe input minimum voltage
YB5
bar
2.90
Pressure matching the B2 probe input maximum voltage
TH5
V
2.50
Upper pressure limit for fault F82 activation: 0÷9.99
Hydraulic circuit WATER FLOW control
S6
3
Flow sensor B3 input enabling: 0=disabled
1=enabled as ON/OFF input without F85 fault autoreset
2=enabled as ON/OFF input with F85 fault autoreset
3=enabled as pulsed input without F85 and F86 fault autoreset
4=enabled as pulsed input with F85 and F86 fault autoreset
ST6
From l/h
56
Flowmeter setpoint - in l/h (x10)
P6
5
ST6 hysteresis: - in l/h (x10)
XA6
Hz
14
B3 pressure probe signal input minimum frequency: 0÷999
XB6
Hz
229
B3 pressure probe signal input maximum frequency: 0÷999
YA6
l/h
29
Flow rate matching the B3 probe inlet minimum frequency
YB6
l/h
500
Flow rate matching the B3 probe inlet maximum frequency
TR6
sec
2
Fault F85/F86 indication time delay (1=1second): 0÷250. During the ignition
stage, the b15 value is used.
Содержание Aermax Series
Страница 2: ...2 code HC0100 00GB ed A 1509 HY AQUAPUMP HYBRID HYBRID HEATER...
Страница 4: ...4 code HC0100 00GB ed A 1509 HY AQUAPUMP HYBRID HYBRID HEATER...
Страница 5: ...5 code HC0100 00GB ed A 1509 HY AQUAPUMP HYBRID HYBRID HEATER...
Страница 6: ...6 code HC0100 00GB ed A 1509 HY AQUAPUMP HYBRID HYBRID HEATER...
Страница 60: ...60 code HC0100 00GB ed A 1509 HY AQUAPUMP HYBRID HYBRID HEATER...