Maintenance
72
MAXXfl o EVO
6.5 ERROR CODES
Error
Code
Error Code Description
Diag.
Code
Notes
20
Boiler temperature 1, sensor
error
Other
Boiler fl ow sensor (B2) is outside normal limits
439
Boiler fl ow sensor (B2) is short-circuit
440
Boiler fl ow sensor (B2) is open-circuit
26
Common fl ow temperature
sensor error
Any
Check connections or replace faulty sensor located on com-
mon fl ow pipe work up stand section (B10)
28
Flue gas temperature, sensor
error
539
543
Flue gas sensor (B8) is short-circuit
540
544
Flue gas sensor (B8) is open-circuit
40
Return temperature 1, sensor
error
Other
Boiler fl ow sensor (B7) is outside normal limits
441
Boiler fl ow sensor (B7) is short-circuit
442
Boiler fl ow sensor (B7) is open-circuit
50
DHW temperature 1, sensor
error
Any
Check connections or replace faulty DHW tank sensor (B3)
81
LPB short-circuit or no power
supply
Any
LPB Short circuit or no bus power supply. Check operation of
OCI345 modules and connecting cables
82
LPB address collision
Any
LPB address duplicated on another Control PCB - Check ad-
dress of all control PCBs via parameter 6600
83
BSB short circuit
Any
No BSB communication or wires shorted - Check operation of
GUI or OZW672 (if fi tted)
84
BSB address collision
Any
Two appliances connected through BSB (e.g. OZW672) have
the same allocation address. Change one of the appliances
address via parameter 6600
98
Extension module 1, error
Any
AGU2.5 confi guration error - Check parameters
99
Extension module 2, error
Any
AGU2.5 confi guration error - Check parameters
100
More than one clock time
master
Any
Only one device should be set as the time master, check on
the GUI (parameter 6640) and any OZW672 connected (in
case of connection to an OZW672, this device should be the
master)
102
Clock master without power
reserve
Any
The control PCB battery backup for the time clock has been
depleted following the restoration of power to the heater. If this
message has not cleared within 10 minutes of power being
turned on, turn the power off , wait 10 seconds and turn the
power on again. This message does not prevent the operation
of the heater in any way.
105
Maintenance message
Any
Item requiring attention but not preventing appliance operation
(e.g. 12 Month service due). Check details of message on the
appliance Front GUI screen.
Содержание MAXXflo EVO CWH 30/201