Installation
34
MAXXfl o EVO
4.7.13
FLUE TERMINAL POSITIONS - C
13
C
33
C
53
C
63
TYPE (CONCENTRIC / TWIN)
Code Minimum distance
mm
A
Directly below an opening, air brick, opening window etc
300
B
Above an opening, air brick, opening window etc
300
C
Horizontally to an opening, air brick, opening window etc
300
D
Below gutters, soil pipes or drainpipes
75
E
Below eaves
200
F
Below a balcony or car port roof
200
G
Above ground, roof or balcony level
300
H
From vertical drain or soil pipe
150
J
From an internal or external corner to an alongside boundary
300
K
From a terminal facing a terminal
1,200
L
Vertically from a terminal on the same wall
1,500
M
Horizontally from a terminal on the same wall
300
N
From a surface or a boundary line facing a terminal
600
P
From a opening in a carport (e.g. door, windows) into the building
1,200
Q
Above a pitched roof
300
R
From a roof structure
2,500
S
Above a fl at roof
300
From any other roof fl ue terminal
300
Terminals should be so
positioned as to avoid
products of combustion
entering openings into
buildings or other
fl
ues or
vents