Maintenance
55
MAXXfl o EVO
6.2 REMOVING AND CHANGING COMPONENTS
NONE OF THE CONTROLS ARE REPAIRABLE . IF THEY ARE NOT FUNCTIONING THEY MUST BE
REPLACED In all cases, before work commences turn o
ff
the mains electricity and gas supply.
The following items do not require isolating water before removal:
•
DHW tank temperature sensor (B3)
•
Flue temperature sensor (B8)
•
AVS37 GUI display
•
LMS14 PCB Replacement
•
Spark generator
•
Combustion fan
•
Overheat thermostat
•
Gas valve
•
Electrode removal
•
Back fl ow prevention fl ue valve
The following items require isolation of water before removal and bleeding air afterwards:
•
Heat exchanger
•
Circulation pump
See the following sections for an explanation on how to change these components:
6.2.1 DHW TANK TEMPERATURE SENSOR (B3)
• Remove and withdraw the foam insulation above the top of the tank
• Gently pull the sensor up the dip tube
• Undo the bulkhead seal and pull the sensor through to the front.
• Unplug connector from loom.
• Cut off securing tie and remove sensor.
• Replacement is the reverse.
Bulkhead seal
Sensor
Remove cable tie
R
R
Sensor connector