background image

  

 

 

Amphenol Network Solutions 

All rights reserved. 12.18.19 139688-3 

509.926.6000 – amphenol-ns.com 

100A Dual-Feed 

Breaker Panel

 

Remember: Output wires must be rated at or above the amperage rating of the output circuit breaker. For 

example, use no smaller than #12 AWG output wiring for 20A output fuses. Do not exceed 16A 

continuous load for a 20A breaker

.  

 

 

 

ALERT! Local electrical and operating company guidelines recommend that the individual load 

not exceed 80% of circuit breaker capacity (for example, 10A breaker x .80 = 8A max. load). 

 

Total load for all breaker outputs on each side 

must not exceed 100A.  

 

18. Clean output terminals and lugs with a nonabrasive, nonmetallic pad.  
19. If covers are installed, remove the covers over the output and alarm connectors.  
20. Amphenol Network Solutions recommends that you lightly coat antioxidant on lugs and output 

BATTERY

 and 

RETURN

 terminals before connecting lugs/wires to outputs. (NEC specifies only one 

lug and load for each output terminal.) Tighten the screws to 9 in.-lb (1.01 N

m).  

21. Connect the other end of output wires to 

load. 

 

22. Use the designation labels (supplied) to record  

outputs, as specified by operating company  

standard installation procedures.  

23. Make sure inputs at 

loads are disabled 

by  

removing all power cards or all input fuses 

at load equipment.  

 

Always follow recommended operating  

company guidelines when disabling  

load equipment. 

 

24. 

One by one

, turn on circuit breakers on this  

panel and check voltage and polarity at 

input of loads. 

 

25. With all circuit breakers on, the 

BREAKER ALARM

 LED must go off. Test fuse alarm relay contacts 

at 

FUSE ALARM

 terminals on rear of panel:  

  Expect continuity (0

Ω

)

 between Terminals 

C

 and 

NC

.  

  Expect an open circuit (

∞Ω

) between Terminals 

and 

NO

.  

 

26. Switch off one of the circuit breakers to simulate a tripped breaker.  

 

Again, the 

BREAKER ALARM

 LED should light.  

 

27. Press ALARM RESET on front of panel.  

 

The 

BREAKER ALARM

 LED should go off again. (Pressing ALARM RESET will reset the 

BREAKER 

ALARM

 LED on front and clear 

FUSE ALARM

 on rear of panel.) Recheck the 

FUSE ALARM

 

terminals and expect the same status as in step 25 with all breakers on. 

 

28. If desired, connect remote external audio/visual alarm indicator wires (solid or tinned wires, #30 to 

#16 AWG) to the 

POWER FAIL

 and 

FUSE ALARM

 terminals.  

29. One by one, re-enable load equipment and verify proper operation.  

Figure 8 – Designation Label 

Содержание T009-5030 Series

Страница 1: ...100A Dual Feed Breaker Panel T009 5030XXXXXXX Installation Guide...

Страница 2: ...data and communications markets We design manufacture and distribute products for customers who need an end to end solution for network connectivity fiber power distribution and rack management We co...

Страница 3: ...mary 11 1 6 1 Normal Operation 11 1 6 2 Input Power Failure 11 1 6 3 Output Breaker Opens either being tripped or manually turned off 11 1 7 Schematic Drawing 12 1 8 Assembly Drawing 13 List of Figure...

Страница 4: ...ccessories Page 10 for ordering optional and replaceable items output breakers face plates lugs ETSI mounting kit and more Mechanical Specifications Dimensions nominal without brackets Width Height De...

Страница 5: ...vice rating 125A Maximum continuous load rating total 100A per feed Maximum output interruption device rating 20A per circuit breaker Maximum continuous output load rating 16A per circuit breaker Alar...

Страница 6: ...tion If you need assistance call Amphenol Network Solutions Technical Support at 509 926 6000 or email us at getinfo amphenol ns com Inspect equipment after unpacking and compare it to the packing lis...

Страница 7: ...unused rack position and mount panel using the four screws and lockwashers provided as shown in Figure 3 It s best to mount the panel as high as possible on the rack Tighten screws to 35 in lb 4 29 N...

Страница 8: ...to the panel is turned off 6 Make sure the input power is off 7 For input wiring wiring used as inputs to this distribution panel proceed as follows a Crimp dual hole compression lugs onto suitable co...

Страница 9: ...ress and hold ALARM RESET on front of panel for 5 seconds to verify that all LEDs are in working order 14 With one or all circuit breakers off test fuse alarm relay contacts at FUSE ALARM terminals on...

Страница 10: ...nation labels supplied to record outputs as specified by operating company standard installation procedures 23 Make sure inputs at loads are disabled by removing all power cards or all input fuses at...

Страница 11: ...so it slightly protrudes out of the front of the panel 3 While preventing the breaker from going back into the panel depress the bottom tab with the screwdriver and pull out on the breaker This starts...

Страница 12: ...eaker and check the orientation of the new breaker 12 Press the spade connector of the new breaker into the pliers held LINE connector until it is fully seated Visually inspect the connection to be su...

Страница 13: ...Amphenol Network Solutions Part No 117995 included with your panel Item Description Part Number Alarm Card Power CB LEDs with Alarm Reset 400329 Circuit Breaker1 1A long delay 129316RC 3A long delay...

Страница 14: ...osed b C to NO is open 4 POWER FAIL relay is energized so that a C to NC is closed b C to NO is open 1 6 2 Input Power Failure 1 POWER ON A or POWER ON B LED s will go off 2 POWER FAIL relay de energi...

Страница 15: ...12 Amphenol Network Solutions All rights reserved 12 18 19 139688 3 509 926 6000 amphenol ns com 100A Dual Feed Breaker Panel 1 7 Schematic Drawing Shown in alarm state Not Used Not Used...

Страница 16: ...lutions convey any license under its patent rights or the patent rights of others This document and the products described herein are subject to change without notice 1 70 1 25 23 00 58 4 22 31 56 7 1...

Отзывы: