100A Dual-Feed 

Breaker Panel

 

1.1 Overview

 

 

The Amphenol Network Solutions dual-

feed configurable breaker panel provides 

circuit breaker power protection for a 

variety of telecommunications 

equipment. The panel includes seven 

circuit breakers per side (configurable from 1A to 20A)  

for a total maximum continuous output load  

of 100A per side.  

 

The panel is black with seven Long-Delay breakers, compression inputs and wire-binding screw outputs.  

 

Feeds A and B are completely independent except for the replaceable alarm card which contains power 

and alarm LEDs for both feeds. Also included are breaker alarm and power-fail relay terminals for wiring 

external indicators.  

 

Hardware is included for flush or extended mounting in 19-in. or 23-in. relay racks. See “Accessories” 

(Page 10) for ordering optional and replaceable items: output breakers, face plates, lugs, ETSI mounting 

kit and more. 

 

 

Mechanical Specifications

 

Dimensions (nominal), 

without brackets* 

Width:  

Height:  

Depth:   

17.25 in. (43.82 cm) 

1.75 in. (4.44 cm) 

8.00 in. (20.32 cm) 

Weight without breakers 

9 lbs. (4.08 kg) 

Weight, shipping 

10.5 lbs. (58.4 cm) 

Mounting for standard racks  EIA: 

WECO: 

ETSI: 

19 in. (48.2 cm) 

23 in. (58.4 cm) 

53.3 cm. Kit sold separately. See “1.5 Accessories” on Page 10.  

Ground terminals 

Quantity: 

Stud:  

Lugs: 

 

Cable: 

 

  

Torque: 

M5 with hex nut. [Use 8 mm (5/16 in.) socket.] 

Single- or dual-hole compression lug (5/8 in. [1.59 cm]  

center to center) 

Up to #10 AWG for single-hole lug 

Up to #6 AWG for dual-hole lug 

(Conductor size depends on input interruption device.) 

20 in.-lb (~2.25 N

m), max.  

Input terminals — 

compression 

Quantity:  

Stud:  

Lugs:  

Cable:  

Torque: 

4—2 BATT, RTN 

M5 with KEPS nut. [Use 8 mm (5/16 in.) socket.] 

Dual-hole compression lug (5/8 in. [1.59 cm] center to center) 

Up to #1 AWG, depending on input interruption device 

20 in.-lb (~2.25 N

m), max.  

 

 

 

Front 

Rear 

Figure 1 – 100A Dual-Feed Breaker Panel 

Содержание T009-5030 Series

Страница 1: ...100A Dual Feed Breaker Panel T009 5030XXXXXXX Installation Guide...

Страница 2: ...data and communications markets We design manufacture and distribute products for customers who need an end to end solution for network connectivity fiber power distribution and rack management We co...

Страница 3: ...mary 11 1 6 1 Normal Operation 11 1 6 2 Input Power Failure 11 1 6 3 Output Breaker Opens either being tripped or manually turned off 11 1 7 Schematic Drawing 12 1 8 Assembly Drawing 13 List of Figure...

Страница 4: ...ccessories Page 10 for ordering optional and replaceable items output breakers face plates lugs ETSI mounting kit and more Mechanical Specifications Dimensions nominal without brackets Width Height De...

Страница 5: ...vice rating 125A Maximum continuous load rating total 100A per feed Maximum output interruption device rating 20A per circuit breaker Maximum continuous output load rating 16A per circuit breaker Alar...

Страница 6: ...tion If you need assistance call Amphenol Network Solutions Technical Support at 509 926 6000 or email us at getinfo amphenol ns com Inspect equipment after unpacking and compare it to the packing lis...

Страница 7: ...unused rack position and mount panel using the four screws and lockwashers provided as shown in Figure 3 It s best to mount the panel as high as possible on the rack Tighten screws to 35 in lb 4 29 N...

Страница 8: ...to the panel is turned off 6 Make sure the input power is off 7 For input wiring wiring used as inputs to this distribution panel proceed as follows a Crimp dual hole compression lugs onto suitable co...

Страница 9: ...ress and hold ALARM RESET on front of panel for 5 seconds to verify that all LEDs are in working order 14 With one or all circuit breakers off test fuse alarm relay contacts at FUSE ALARM terminals on...

Страница 10: ...nation labels supplied to record outputs as specified by operating company standard installation procedures 23 Make sure inputs at loads are disabled by removing all power cards or all input fuses at...

Страница 11: ...so it slightly protrudes out of the front of the panel 3 While preventing the breaker from going back into the panel depress the bottom tab with the screwdriver and pull out on the breaker This starts...

Страница 12: ...eaker and check the orientation of the new breaker 12 Press the spade connector of the new breaker into the pliers held LINE connector until it is fully seated Visually inspect the connection to be su...

Страница 13: ...Amphenol Network Solutions Part No 117995 included with your panel Item Description Part Number Alarm Card Power CB LEDs with Alarm Reset 400329 Circuit Breaker1 1A long delay 129316RC 3A long delay...

Страница 14: ...osed b C to NO is open 4 POWER FAIL relay is energized so that a C to NC is closed b C to NO is open 1 6 2 Input Power Failure 1 POWER ON A or POWER ON B LED s will go off 2 POWER FAIL relay de energi...

Страница 15: ...12 Amphenol Network Solutions All rights reserved 12 18 19 139688 3 509 926 6000 amphenol ns com 100A Dual Feed Breaker Panel 1 7 Schematic Drawing Shown in alarm state Not Used Not Used...

Страница 16: ...lutions convey any license under its patent rights or the patent rights of others This document and the products described herein are subject to change without notice 1 70 1 25 23 00 58 4 22 31 56 7 1...

Отзывы: