Message and Type
Comment
Outlet Paused
2
IPM waits 5 sec between running (or testing) and re-
testing
Need IPM Start
2
Awaiting IPM start digital input
Testing Insulation
2
In process of Insulation Test (2 seconds)
Closing Main Cont.
2
MCR closed, waiting on MCI feedback (5 sec max.)
Burp: MCR Closed
2
Burp Phase is on MCR closed
Burp: MCR Open
2
Burp phase is active
– MCR is open
Running
2
Outlet closed
Snore
2
Snore function active
Snore
– Close AUX
2
Aux digital input must be closed for Snore to function
High Current Alarm
2
High Current Alarm triggered
Thermal Trip Alarm
2
Thermal Trip Alarm triggered
Cur. Balance Alarm
2
Current Balance Alarm triggered
Under Cur. Alarm
2
Under Current Alarm triggered
Earth Leakage Alarm
2
Earth Leakage Alarm triggered
UnderVoltage Alarm
2
Under Voltage Alarm triggered
Insulat. Test Alarm
2
Insulation Test Alarm triggered
Need RTM Start
2
Shown when the digital input is closed but the IPM is
stopped
OTS Testing Mode
2
IPM operating in OTS Test Mode
Earth Leakage Trip
3
Earth Leakage function tripped
Earth Cont. Trip
3
Earth Continuity function tripped
Insulat. Fail Trip
3
Insulation Test function tripped
Over Current Trip
3
Over Current function tripped
Short Circuit Trip
3
Short Circuit function tripped
I Balance Trip
3
Phase Current Balance function tripped
Residual Cur. Trip
3
Residual Current function tripped
Main Contactor Fail
3
Main Contactor Fail function tripped
RTM-Offline Trip
3
IPM cannot communicate with RTM
IPM Memory Error (see
Note 1)
3
Corrupted memory in relay‟s stored settings