Event
Description
one outgoing phase when the main contactor was
closed
Ires.trip
Residual E/L Trip condition
Tmem Loss
The thermal memory data has been corrupted
T-mem Rst
Thermal memory has been manually reset to zero
Mem.ERROR
Records that the relay‟s non-volatile parameter
memory has been corrupted
µ- P reset
Internal microprocessor reset
RTM mem. E
Records that the Remote
Termination Module‟s
non-volatile memory has been corrupted or Remote
Termination Module has gone off line while the
outlet is running.
Feeder On
Records RTM machine code and number when
main contactor is closed (proceeded by MCR
closed). This log only appears when in RTM mode.
RTM Off L
Indicates a loss of communications with the RTM.
Meg Ω Trp
Insulation Test failed
IT: -- . -M
Ω
Records the result of the Insulation Test
Insul.Alm
Result of Insulation Test is equal to or less than the
alarm level
o/l alarm
Thermal accumulator has exceeded the selected
threshold
L-cur alm
Phase current has dropped below the selected
threshold
H-cur.alm
Phase current has exceeded the selected threshold
e/l alarm
Earth leakage current exceeded the selected
threshold
RTM Stop
In any of the remote start modes; the event log will
record when the IPM is stopped via the remote
digital input.
12.10 Time and Date
Clock Setup
We 26/07 14:58:21
If there is a need to adjust the real time clock, carry out the following procedure:
Using the d
isplay‟s keys select the time and date information page (Level 4, Screen 5) to display
the Day, Month, Year, Hours and Minutes.
Press the ENTER
key. A “v” will appear in the top line above the minute section. This indicates
the number to be changed.
Use the left and right arrow keys to move the “v” to the desired position.
Press the ENTER
key. The “v” now changes to a “?” The right arrow key is used to increment the
allowable values, once the desired value is obtained, press the ENTER
key again. The “?”
returns to a “v”.