GASGUARD IS CONTROLLER Issue: R2, Date: 26/09/2011, CRN: 7502
Page 40
10
Data Communication Specification
Communication Port: RS485
Protocol: Standard Modbus Protocol – RTU Mode
Baud rate: 2400, 4800, 9600, 19200 bps. Parity: Even, Odd, None, Data bits: 8, Modbus Slave Address: 1- 32
10.1
Modbus Memory Map Part 1
10.1.1
Memory Type 0:
Modbus Address
Description
Data Format
00001
Relay 1 Status
1
Relay is Active
0
Relay is Normal
00002
Relay 2 Status
00003
Relay 3 Status
00004
Relay 4 Status
Available Modbus Function code is 0x01 (Read Coil Status).
10.1.2
Memory Type 1:
Modbus Address
Description
Data Format
10001
Channel 1 Low Fault
1
Fault /Alarm State
0
Normal
10002
Channel 1 Alarm 1
10003
Channel 1 Alarm 2
10004
Channel 1 Alarm 3
10005
Channel 1 High Fault
10006
Channel 1 Spare
10007
Channel 1 Spare
10008
Channel 1 Spare
10009
Channel 2 Low Fault
10010
Channel 2 Alarm 1
10011
Channel 2 Alarm 2
10012
Channel 2 Alarm 3
10013
Channel 2 High Fault
10014
Channel 2 Spare
10015
Channel 2 Spare
10016
Channel 2 Spare
10017
Channel 3 Low Fault
10018
Channel 3 Alarm 1
10019
Channel 3 Alarm 2
10020
Channel 3 Alarm 3
1
Fault /Alarm State
0
Normal
10021
Channel 3 High Fault
10022
Channel 3 Spare
10023
Channel 3 Spare
10024
Channel 3 Spare
10025
Channel 4 Low Fault
10026
Channel 4 Alarm 1
10027
Channel 4 Alarm 2
10028
Channel 4 Alarm 3
10029
Channel 4 High Fault
10030
Channel 4 Spare
10031
Channel 4 Spare
10032
Channel 4 Spare
10033
Zone 1 Status
1
Zone Active
0
Zone Normal
10034
Zone 2 Status
10035
Zone 3 Status
10036
Zone 4 Status
10037
Zone 5 Status
10038
Zone 6 Status
Available Modbus function code is 0x02 (Read Input Status)
Содержание gasguard
Страница 46: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 45 10 2 Modbus Memory Map Part 2 ...
Страница 47: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 46 ...
Страница 49: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 48 A2 Top Level Functional Block Diagram ...
Страница 50: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 49 A3 Input Channel Functional Block Diagram ...
Страница 51: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 50 A4 Zoning Functional Block Diagram ...
Страница 52: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 51 A5 Relay Functional Block Diagram ...
Страница 53: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 52 A6 Current Follower Outputs Performance Graph ...
Страница 62: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 61 B2 Main Menu Flowchart ...
Страница 63: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 62 B3 Calibration Flowchart ...
Страница 64: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 63 B4 Configuration Flowchart ...
Страница 65: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 64 Configuration Flowchart con t ...
Страница 66: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 65 Configuration Flowchart con t ...
Страница 74: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 73 Appendix C Approvals ...
Страница 75: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 74 ...
Страница 76: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 75 ...
Страница 77: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 76 ...
Страница 78: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 77 ...
Страница 79: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 78 ...