GASGUARD IS CONTROLLER Issue: R2, Date: 26/09/2011, CRN: 7502
Page 25
4.2.8
Setting Alarm or Fault Levels
To set alarm or fault levels use the procedure for the Low / High Fault Alarm following. The same three steps can be
carried out on all alarm/faults by scrolling down the menu to the required area and inputting the correct information.
4.2.9
Set Low / High Fault Alarm Level
1.
To modify ‘LF’ press
to enter
2.
Use the
key to scroll through the numbers
3.
Use the
key to move the cursor across to the next digit
4.
To save, use the
key
5.
To escape, use the
key
4.2.10
Set Low / High Fault Alarm Direction
1.
To modify ‘LF DIR’ press
to enter
2.
Use the
key to toggle between Falling/Rising
3.
To save, use the
key
4.
To escape, use the
key
4.2.11
Set Low / High Fault Alarm Latch
1.
To modify ‘LF Latch’ press
to enter
2.
Use the
key to toggle between YES and NO
3.
To save, use the
key
4.
To escape, use the
key
4.2.12
Set Alarm Delay
1.
To modify ‘ALM DLY’ press
to enter
2.
Use the
key to scroll through the numbers
3.
Use the
key to move the cursor across to the next digit
4.
To save, use the
key
5.
To escape, use the
key
4.2.13
Set Alarm Hysteresis
1.
To modify ‘A1 HYST’ press
to enter
2.
Use the
key to scroll through the percentages
3.
Use the
key to move the cursor across to the next digit
4.
To save, use the
key
5.
To escape, use the
key
6.
To set A2 and A3 Hysteresis levels, recompleted steps 1 through 5
Содержание gasguard
Страница 46: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 45 10 2 Modbus Memory Map Part 2 ...
Страница 47: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 46 ...
Страница 49: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 48 A2 Top Level Functional Block Diagram ...
Страница 50: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 49 A3 Input Channel Functional Block Diagram ...
Страница 51: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 50 A4 Zoning Functional Block Diagram ...
Страница 52: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 51 A5 Relay Functional Block Diagram ...
Страница 53: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 52 A6 Current Follower Outputs Performance Graph ...
Страница 62: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 61 B2 Main Menu Flowchart ...
Страница 63: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 62 B3 Calibration Flowchart ...
Страница 64: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 63 B4 Configuration Flowchart ...
Страница 65: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 64 Configuration Flowchart con t ...
Страница 66: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 65 Configuration Flowchart con t ...
Страница 74: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 73 Appendix C Approvals ...
Страница 75: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 74 ...
Страница 76: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 75 ...
Страница 77: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 76 ...
Страница 78: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 77 ...
Страница 79: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 78 ...