Decimal Point
Each Input channel may have its display reading configured to correctly indicate the process value.
The available settings for decimal places are:-
•
nnnn (e.g. 2500)
•
nnn (e.g. 250)
•
nn.n (e.g. 25.0)
•
n.nn (e.g. 2.50)
Full Scale Reading
Input process signals to the controller are typically in the range 4 – 20mA and as such may represent a variety of
actual process scaling. To set the relationship between 4-20mA input and the process scaling, the channel full scale
value may be set. Settings are per digit, with up to four digits available. The displayed value of this setting will
depend on the decimal place setting.
The maximum value that may be set is to be 9999 (999 / 99.9 / 9.99 depending on decimal point position)
Units
The process displayed readings can be given units of measurement indicator. There are ten pre-set unit types
available for selection, namely:-
•
%v/v (percent volume per volume)
•
ppm (parts per million)
•
LEL (Lower Explosive Limit)
•
% (percent)
•
V (volts)
•
mV (millivolts)
•
rpm (revolutions per minute)
•
Hz (cycles per second)
•
kHz (thousands of cycles per second)
•
m/s (meters per second)
Tag
A channel may be given an identification name that provides meaningful representation of its purpose/function within
a system. The tag input is entered as a 9 character name consisting of the following characters:-
•
Symbols: blank * - + .
•
Numeric: 0 – 9
•
Alpha A-Z (uppercase only)
Содержание gasguard
Страница 46: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 45 10 2 Modbus Memory Map Part 2 ...
Страница 47: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 46 ...
Страница 49: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 48 A2 Top Level Functional Block Diagram ...
Страница 50: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 49 A3 Input Channel Functional Block Diagram ...
Страница 51: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 50 A4 Zoning Functional Block Diagram ...
Страница 52: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 51 A5 Relay Functional Block Diagram ...
Страница 53: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 52 A6 Current Follower Outputs Performance Graph ...
Страница 62: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 61 B2 Main Menu Flowchart ...
Страница 63: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 62 B3 Calibration Flowchart ...
Страница 64: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 63 B4 Configuration Flowchart ...
Страница 65: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 64 Configuration Flowchart con t ...
Страница 66: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 65 Configuration Flowchart con t ...
Страница 74: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 73 Appendix C Approvals ...
Страница 75: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 74 ...
Страница 76: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 75 ...
Страница 77: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 76 ...
Страница 78: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 77 ...
Страница 79: ...GASGUARD IS CONTROLLER Issue R2 Date 26 09 2011 CRN 7502 Page 78 ...