Ampcontrol Pty Ltd
– ABN 28 000 915 542
GG2 DISPLAY USER MANUAL
GG2B023 Version 3
– JUNE/19
Uncontrolled Copy - Refer to Ampcontrol Website for Latest Version
Page 71 of 82
A
P
P
R
OV
E
D
FOR
E
X
T
E
R
N
A
L
D
IS
TR
IB
U
T
ION
–
P
R
OP
E
R
T
Y
OF
A
M
P
C
ON
TR
OL
P
T
Y
LTD
–
N
O
T
T
O
B
E
R
E
P
R
OD
U
C
E
D
I
N
P
A
R
T
Block,
Parameter
Label
Description of 16-bit word
R/W
5,0
Last linearity test number of test
points
R
5,1
General Status word
Bit 0: Set bypass mode. 1= bypassed.
Flashes FAULT LED and displays
message on screen; unit still operates, Bit
1: Reset latched catalytic (change from 0
to 1 after sensor latches for reset), Bit
2:detector warming up
R
5,2
linearity test timestamp lo-word
R
5,3
linearity test timestamp hi-word
R
6,0
Detector type (incl gas units)
Some table for each of the gasses being
done.
R
6,1
Detector Serial number low word
Detector CSM serial number
32 bits (for calibration tracking)
R
6,2
Detector Serial number high word
R
6,3
Detector Software Version
16 bit version number of some description
R
7,0
Display Serial number low word
Display CSM serial number
32 bits (for overhaul tracking)
R
7,1
Display Serial number high word
R
7,2
Display Base Software Version
16 bit version number of some description
R
7,3
Display Application Software
Version
16 bit version number of some description
R
7.3.1.3 Analogue Input
Analogue Input Register - polled, available in data tables
Bit
Description
Bit value
Notes
0-15
4-20mA input value
0-20,000 typical
May be scaled using the Engineering Units
fields in the Status Flags Programming
Parameters. Never scaled in the field.
Analogue Input Programming Parameters - available via rollcall only
Block,
Parameter
Label
Description of 16-bit word
1,0
iMAC Address
0-255; iMAC address for Analogue Input
1,1
Set point 1
Setpoint for exception trigger between 4000-20000
1,2
Set point 2
Setpoint for exception trigger between 4000-20000
1,3
Set point 3
Setpoint for exception trigger between 4000-20000