Register
Description
R/W
Detail
Format
6
– bit 8
4-20mA loop fault
R
1 = 4-20mA loop fault
bit
i6
– bit 9
Latched catalytic detector
R
1 = detector latched
bit
6
– bit 10
Hardware fault
R
1 = fault
bit
6
– bit 11
Detector warmup
R
1 = in warmup
bit
6
– bit 12
Data valid
R
1 = data valid
bit
6
– bit 13
Sensor aged. Sensor
performance has deteriorated
due to age.
R
1 = sensor aged
bit
6
– bit 14
Out of operational temp range.
R
1 = temp out of range
bit
6
– bit 15
Telemetry test active
R
1 = telemetry test in progress
bit
7
RESERVED
8
– bit 0
System bypass
R/W Write 1 to put device into
bypass. Write 0 to leave
bypass.
bit
8
– bit 1
Reset latched catalytic
R/W Write 1 to activate the reset,
the value should clear to 0.
bit
9
– bits 0-
7
FACTORY USE ONLY
9
– bit 8
Atmospheric pressure
fluctuation too great to obtain
stable reading
R
1 = true
bit
9
– bit 9
Sensor reading has gone above
100%
R
1 = above range
bit
9
– bit 10
Sensor reading has gone below
-10%. Auto clears when reading
goes above 0%
R
1 = under range
bit
9
– bit 11
FACTORY USE ONLY
9
– bit 12
Unexpected calibration values
R
1 = calibration values are not
correct
bit
9
– bits
13-15
RESERVED
10
– bits
0-11
FACTORY USE ONLY
10
– bit 12 Detector warming up
1 = in warmup
bit
10
– bit 13 Catalytic latch
1 = detector latched
bit
10
– bit 14 Incomplete adjustment (NDIR)
1 = adjustment incomplete
bit
10
– bit 15 FACTORY USE ONLY
11
Detector pressure
Hectopascals (hPa)
Signed Int
12
Detector temperature
Degrees Celsius(°C) * 100
Signed Int
13
Detector humidity
Permyriad
Signed Int
14
Detector bus voltage
Millivolts
Signed Int
7.2.1.3 ID Info
Register
Description
R/W
Detail
Format
15
Maximum engineering unit
value
R
Real world gas value
– span
Signed Int
16
Minimum engineering unit value
R
Real world gas value
– zero
Signed Int
17
Engineering unit number of
decimal places
R
Unsigned Int