How to set the Alarms on THE BARRACUDA MODEL 4010LX
?
THE BARRACUDA MODEL 4010LX
comes standard with two fully, adjustable independent alarms
(ALARM ONE and ALARM TWO) that can be adjusted over
THE BARRACUDA
'
s entire moisture
measurement range.
To set ALARM ONE, press the ALARM ONE Button and quickly release. The LCD alarm flag will blink,
and within 3 seconds, press either the UP or DOWN buttons to set your alarm setpoint. Once pressed,
just hold the button until you reach your desired alarm setpoint. The longer you hold, the faster the alarm
setpoint adjusts. If no buttons are pressed within 3 seconds, the Analyzer will revert to measurement
mode.
If you make a mistake at any time, simply let go of the button for 3-4 seconds, and the LCD will return to
measurement mode. Then try again.
Note: If you want to adjust any other alarm settings, you must do so through the
COMMAND CENTER
.
To set ALARM TWO, repeat the same steps as used in ALARM ONE.
How to set the Alarm Hold Off
?
Press the ALARM HOLD OFF button, and the Alarm Hold Number will appear. And within 3-4 seconds,
push either the UP or DOWN Button to adjust the duration of your ALARM HOLD OFF. The ALARM
HOLD OFF can be engaged from 0 to 120 minutes.
After the time for setting the ALARM HOLD OFF expires, both Alarms and the Analog Output will revert
to measurement mode.
ADDITIONAL NOTES
:
If you need more time for the setup, simply push the ALARM HOLD OFF Button again, and it will
automatically reset to the adjusted Hold Off Time.
If you complete the calibration task quicker than expected and want the Alarms and Analog Output to
become functional immediately, you can simply run the Hold Off Time to zero by pushing the Hold Off
Button until the LCD blinks and then pushing the DOWN ARROW until the LCD shows zero.
Alarm Two
Alarm One
Up and Down
Adjust Buttons
Up and Down
Adjust Buttons
Alarm Hold off
21