or external to the building. In cold climates, it is recommended 
that the discharge pipe be terminated at an adequate drain 
inside the building.

•   Shall not have any valve between the relief valve and tank.

When installing the temperature-pressure relief valve, use 
two or three turns of Teflon® tape or other suitable thread 
sealer around the threaded end of the valve.

Figure 2.

The temperature-pressure relief valve should be manually 
opened once a year. Caution should be taken to ensure that 
(1) no one is in front of or around the outlet of the 
temperature-pressure relief valve discharge line, and (2) 
the water manually discharged will not cause any bodily 
injury or property damage because the water may be 
extremely hot.

If after manually operating the valve, it fails to completely 
reset and continues to release water, immediately close 
the cold water inlet to the water heater, follow the draining 
instructions, and replace the temperature-pressure relief 
valve with a new one.

I

f the temperature-pressure relief valve on the appliance 

weeps this may be due to thermal expansion. The water 
supply serving this solar water heater may have a check 
valve installed.  Contact the water supplier or local plumbing 
contractor on how to control this situation.  Do not plug the 
temperature-pressure relief valve.

CLOSED SYSTEM/THERMAL EXPANSION 

As water is heated, it expands (thermal expansion). In a 
closed system, the volume of water will grow. As the volume 
of water grows, there will be a corresponding increase 
in water pressure due to thermal expansion. Thermal 
expansion can cause premature tank failure (leakage). This 
type of failure is not covered under the limited warranty. 
Thermal expansion can also cause intermittent temperature-
pressure relief valve operation: water discharged from the 
valve due to excessive pressure build up. The temperature-
pressure relief valve is not intended for the constant relief 
of thermal expansion. This condition is not covered under 
the limited warranty.

A properly-sized thermal expansion tank should be installed 
on all closed systems to control the harmful effects of 
thermal expansion. Contact a plumbing service agency or 
your retail supplier regarding the installation of a thermal 
expansion tank..

LOCATING THE SOLAR WATER HEATER 

If you have a choice of where to install the solar water heater, 
these ideas may help you decide.

1.  Put the solar water heater indoors as close as possible 

to where you use the most hot water. This water heater 

is not intended for outdoor installation.

2.  It is handy to have a floor drain, tub or sink nearby. 

That will make it easy to drain water from the water 
heater. It is also a good place to end the drain line of 
the temperature-pressure relief (T & P) valve.

3.  The solar water heater or the pipes and the connections 

may, in time, leak.  Put the solar water heater in a place 
where a water leak will not damage anything.  

4.  You must not put the water heater in an area where 

it might freeze You must turn off the electricity to the 
water heater before you drain it, to protect the heating 
elements.

5.  Make sure that you are able to reach the drain valve 

and all access panels when the water heater is in place.  
This will make it easy to service the water heater.

6.  The water heater must be level before you begin the 

piping.

WATER HEATERS EVENTUALLY LEAK.

 The installation 

of the water heater must be accomplished in such a manner 
that if the tank or any connections should leak, the flow 
of water will not cause damage to the area adjoining the 
water heater or to lower floors of the structure. When such 
locations can’t be avoided, a suitable metal drain pan should 
be installed under the water heater. Such a pan should be 
no greater than 1 1/2 inches deep, have a minimum length 
and width of at least two inches greater than the heater 
dimensions and must be piped to an adequate drain. 

This solar water heater, as all water heaters, will eventually 
leak. Do not install without adequate drainage provisions 
where water flow will cause damage. Note: normal 
condensation from a solar water heater may appear to be 
a leaking tank.

WATER PIPING 

This solar water heater is design certified to be used with a 
potable water system. When connecting water piping with 
solder joints use only lead free solder.

This solar water heater shall not be connected to any 
heating systems or component(s) previously used with a 
non-potable water heating appliance.

If this solar water heater is also used for space heating 
applications, all piping and components connected to the 
solar water heater shall be suitable for use with potable 
water.

This appliance has been design certified as a solar water 
heater complying with Standards for Safety - UL174 for 
the U.S. and can/csa-c22.2 No 110 F379.1 and F379.2 

Содержание SRCC OG-100

Страница 1: ...TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOUARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER Instruction Manual RESIDENTIAL SOLAR WAT...

Страница 2: ...he water heater as they relate to the installation of electric water heaters The qualified installer must have a thorough understanding of the water heater Instruction Manual Service Agency A service...

Страница 3: ...3 GENERAL SAFETY...

Страница 4: ...erated to keep the water hot throughout the rest of the day and night However on days when the sky is cloudy or when large quantities of hot water are being used we recommend leaving the backup heater...

Страница 5: ...R COLLECTOR INSTALLATION 13 Collector Location 13 General Considerations 13 Collector Orientation 13 14 Spanner Mounting 15 17 Attaching Collector to Mounting Brackets 18 Collector Piping 19 Collector...

Страница 6: ...G THE SOLAR WATER HEATER SECTION INSTALL THERMAL EXPANSION TANK OR DEVICE IF WATER HEATER IS INSTALLED IN A CLOSED WATER SYSTEM 6 Maximum Air Gap Piped To An Adequate Drain At Least 2 Greater Than The...

Страница 7: ...PRESSURE RELIEF VALVE For protection against excessive pressures and temperatures in this water heater install temperature pressure protective equipment required by local codes but not less than a com...

Страница 8: ...e a choice of where to install the solar water heater these ideas may help you decide 1 Put the solar water heater indoors as close as possible to where you use the most hot water This water heater is...

Страница 9: ...ater heater is installed in a closed water system such as one having a back flow preventer check valve or water meter with check valve in the cold water supply line means shall be provided to control...

Страница 10: ...t voltage can cause problems which can result in DEATH SERIOUS BODILY INJURY OR PROPERTY DAMAGE If you have any questions or doubts consult your electric company If wiring from the fuse box or circuit...

Страница 11: ...rclockwise to decrease the temperature 4 Fold the insulation back in place and replace the access panel 5 Turn ON the power supply A non adjustable high temperature limit control operates before steam...

Страница 12: ...al anode rod may be available if water odor or discoloration occurs NOTE This rod may reduce but not eliminate water odor problems The water supply system may require special filtration equipment from...

Страница 13: ...rated assemblies Ensure the mounting surface is solid and able to with stand in excess of 330lbs 150kg of pull force that may be encountered during high winds Consult a structural engineer if in doub...

Страница 14: ...204 244 295 9 2 12 69 78 90 104 123 139 157 180 205 14 3 12 63 69 78 88 101 111 123 136 149 18 4 12 59 64 71 78 88 96 105 115 123 23 5 12 54 59 64 70 77 83 89 96 102 27 6 12 52 55 59 64 70 75 80 86 9...

Страница 15: ...en determined that the spanner mounting method is the most suitable for this application Consult with your installer if other mounting means are required for your installation 1 After locating the mou...

Страница 16: ...HORIZONTAL MOUNTING RAFTER MOUNTING BRACKET RAFTER Figure 14 Figure 15 B B C C A DRILL POINTS CLEARANCE HOLE for 5 16 BOLT RAFTER D BASED ON 16 CENTER RAFTERS B B C C A DRILL POINTS CLEARANCE HOLE for...

Страница 17: ...SCREWS FENDER WASHER LOCK WASHER NUT ROOF RAFTER SPACER BLOCK Figure 16 Table 4 IF MOUNTING WITH AN OPTIONAL TILT MOUNT KIT FOR OPTIMAL COLLECTOR ANGLE REFER TO ITS INSTRUCTION SHEET FOR THE APPLICAB...

Страница 18: ...unting brackets prior to raising the collectors The collector can then be set on the lower mounting brack ets while the top clips are fastened over the lip on the collector frame 4 After the solar col...

Страница 19: ...spacing of collectors as attachment of piping is easiest with properly aligned collectors The connection between the collector panels is made with copper unions or couplings To aid in installation th...

Страница 20: ...ration Ensure that all roof penetrations required to plumb and mount the solar collector are properly flashed and sealed in accordance with standard roofing practices The return and supply lines shoul...

Страница 21: ...a com parable level of knowledge specialist The following must be observed during installation and start up Relevant local and national codes Accident prevention regulations of the professional associ...

Страница 22: ...HARGE LINE DRAIN VALVE CONNECTION SET WITH EXPANSION TANK Figure 22 6 Connect a discharge line to the pressure relief valve in the solar circuit 7 Connect the stainless steel corrugated hose to the sa...

Страница 23: ...ed to pump to the tank return threaded fitting Figure 25 FUNCTION Check valves The solar station is equipped with check valves in the supply and the return ball valve J Q For filling venting and flush...

Страница 24: ...priate drain 12 Turn the supply ball valve b to 90 horizontal so that the valve is closed 13 Turn on the supply water and open the fill valve d then leave running for 15 minutes to flush debris out of...

Страница 25: ...st the solar pump speed using the pump speed selector on the side of the pump f Set the speed to the lowest level possible to achieve the recommended system flow rate See Table 5 NUMBER OF COLLECTORS...

Страница 26: ...r loop pump upper primary and one for the water loop pump lower secondary Relay 1 primary pump 18 Line power R1 17 Neutral N 13 Ground Relay 2 secondary pump 16 Line power R2 15 Neutral N 14 Ground Th...

Страница 27: ...d button down for 2 seconds and the system setting screens can then be shown If an adjustable value is shown on the display is indicated To change the set value press the Set button 3 so that flashes...

Страница 28: ...quickly blinking if there is a sensor error Operation control lamp indication Constantly green system operation normal Red green blinking initialization phase manual operation Red blinking sensor err...

Страница 29: ...ssioning menu press button 3 The controller is now ready for operation with typical settings to suit the system layout The settings made in the commissioning menu can be changed later on in the corres...

Страница 30: ...e value for heat quantity will be set to 0 In order to finish the reset procedure the set button 3 must be pressed in order to confirm In order to interrupt the reset procedure no button should be pre...

Страница 31: ...ep If the temperature decreases the secondary pump will decrease by 1 step followed by the primary pump n1MN n2MN Minimum pump speed Adjustment range 30 to 100 Recommended setting 30 A relative minimu...

Страница 32: ...available when OCF is active CFRF Antifreeze temperature off Adjustment range 40 to 50 F Recommended setting 41 F Channel only available when OCF is active O TC Tube collector function Adjustment OFF...

Страница 33: ...MAN1 MAN2 as follows Operating mode OFF relay off flashing AUTO relay in automatic operation ON relay on flashing n1 2 LO minimum speed Note Always adjust the operating mode back to Auto when the cont...

Страница 34: ...valve in solar pump station Inspect valve and repair or replace Cold water supply dip tube Missing or defective Replace dip tube Collectors Absorber coating degradation Replace collector Collector pan...

Страница 35: ...er fuse Repair or replace Flow rated too high or too low Adjust flow rate Faulty pump Listen for irregular noises in pump operation Feel collector feed and return line for temperature difference Ensur...

Страница 36: ...tial set too low Reset off differential according to recommendation Controller set to on position Set system operation to Auto Pump operated but no fluid flows from collectors Air Scoop System air loc...

Страница 37: ...pressure drops unexpectedly contact your installation contractor immediately to diagnose the problem and recharge the system SOLAR PANEL CLARITY If you live in a dusty climate once a month wash off d...

Страница 38: ...Loop Dip Tube w Nipple 9006790005 12 Plastisert Nipple 9003976015 13 T P Valve 9000728015 14 Drain Valve 9003906015 SOLEX DWHX PUMP STATION SERVICE PARTS 15 Temperature Gauge Supply Red 9007789005 16...

Страница 39: ...l Protection Exposure Limits Component List Type Value Propylene glycol Personal Protection Eye Face Protection Use safety glasses Skin Protection Wear clean body covering clothing Hand protection Use...

Страница 40: ...40...

Отзывы: