COLLECTOR PIPING DETAIL 

The outlets of the collector are 1” copper pipe nipples. See 
Figure 19. They should be piped as shown with provisions 
for an air vent. The air vent must be oriented vertically as 
this must be the highest point in the system in order for air 
to escape. This will prevent air lock and subsequent loss of 
system effi ciency. Teflon® tape or high temperature, high 
quality pipe sealant should be used when making threaded 
connections.

The collector inlets should be piped similarly but without 
the air vent.

SENSOR WIRING AT COLLECTOR 

The wiring used to connect the sensors to the controller 
should be a minimum 18 AWG. The wiring should be two-
conductor, PVC UV resistant suitable for outdoor use. Use 
Belden Wire No. 7409A or equivalent. 

SENSOR MOUNTING AT COLLECTOR 

The angled collector heat sensor is mounted to the outlet of 
the collector. See Figure 20. The stainless steel screw clamp 
should be used.  The entire sensor should be wrapped 
thoroughly with insulating stretch tape such as MOCAP 
Silicone X-Treme Tape® so that the sensor is isolated from 
the outside air. If possible route the sensor wire through the 
roof with the collector piping and connect the sensor wire 
to the sensor extension wire with wire nuts.

Figure 20.

PIPING THROUGH THE ROOF 

Preserving the integrity of the roof membrane is the 
most important roofi ng consideration. Ensure that all roof 
penetrations required to plumb and mount the solar collector 
are properly fl ashed and sealed in accordance with standard 
roofi ng practices. 

The return and supply lines should be supported under the 
roof to prevent undue stress on the piping assemblies at 
the collector. Hangers shall provide adequate support and 
correct pitch of pipes. Hangers or supports for insulated 
pipes or components shall avoid compressing or damaging 
the insulation material. Piping should be sloped toward drain 
ports with a drainage slope of no less than 2 cm vertical 
drop for each meter of horizontal length (1/4 inch per foot).

PIPE INSULATION 

The collector loop piping (exterior and interior) must be 
well insulated with a high quality fl exible EPDM closed 
cell insulation to minimize heat loss.  The wall thickness 
of the pipe insulation should not be less than ¾”. A 1” wall 
thickness is required in all areas prone to annual hard 
freeze conditions.  When it comes to pipe insulation the 
rule is simple: thicker is better. The specifi ed  insulation 
material is Armacell UT Solafl ex or equivalent. As part of 
the insulation requirements the fi nal 5 ft of the cold water 
inlet to the storage tank must be insulated.

To the extent possible, slide the insulation material over 
the pipe without cutting or taping. All butt joints must be 
sealed with high temperature contact adhesive. The use 
of rigid polyethylene pipe insulation is prohibited.  All 
outdoor insulation should be protected from moisture and 
Ultraviolet deterioration by either paint or foil tape. 

Содержание SRCC OG-100

Страница 1: ...TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOUARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER Instruction Manual RESIDENTIAL SOLAR WAT...

Страница 2: ...he water heater as they relate to the installation of electric water heaters The qualified installer must have a thorough understanding of the water heater Instruction Manual Service Agency A service...

Страница 3: ...3 GENERAL SAFETY...

Страница 4: ...erated to keep the water hot throughout the rest of the day and night However on days when the sky is cloudy or when large quantities of hot water are being used we recommend leaving the backup heater...

Страница 5: ...R COLLECTOR INSTALLATION 13 Collector Location 13 General Considerations 13 Collector Orientation 13 14 Spanner Mounting 15 17 Attaching Collector to Mounting Brackets 18 Collector Piping 19 Collector...

Страница 6: ...G THE SOLAR WATER HEATER SECTION INSTALL THERMAL EXPANSION TANK OR DEVICE IF WATER HEATER IS INSTALLED IN A CLOSED WATER SYSTEM 6 Maximum Air Gap Piped To An Adequate Drain At Least 2 Greater Than The...

Страница 7: ...PRESSURE RELIEF VALVE For protection against excessive pressures and temperatures in this water heater install temperature pressure protective equipment required by local codes but not less than a com...

Страница 8: ...e a choice of where to install the solar water heater these ideas may help you decide 1 Put the solar water heater indoors as close as possible to where you use the most hot water This water heater is...

Страница 9: ...ater heater is installed in a closed water system such as one having a back flow preventer check valve or water meter with check valve in the cold water supply line means shall be provided to control...

Страница 10: ...t voltage can cause problems which can result in DEATH SERIOUS BODILY INJURY OR PROPERTY DAMAGE If you have any questions or doubts consult your electric company If wiring from the fuse box or circuit...

Страница 11: ...rclockwise to decrease the temperature 4 Fold the insulation back in place and replace the access panel 5 Turn ON the power supply A non adjustable high temperature limit control operates before steam...

Страница 12: ...al anode rod may be available if water odor or discoloration occurs NOTE This rod may reduce but not eliminate water odor problems The water supply system may require special filtration equipment from...

Страница 13: ...rated assemblies Ensure the mounting surface is solid and able to with stand in excess of 330lbs 150kg of pull force that may be encountered during high winds Consult a structural engineer if in doub...

Страница 14: ...204 244 295 9 2 12 69 78 90 104 123 139 157 180 205 14 3 12 63 69 78 88 101 111 123 136 149 18 4 12 59 64 71 78 88 96 105 115 123 23 5 12 54 59 64 70 77 83 89 96 102 27 6 12 52 55 59 64 70 75 80 86 9...

Страница 15: ...en determined that the spanner mounting method is the most suitable for this application Consult with your installer if other mounting means are required for your installation 1 After locating the mou...

Страница 16: ...HORIZONTAL MOUNTING RAFTER MOUNTING BRACKET RAFTER Figure 14 Figure 15 B B C C A DRILL POINTS CLEARANCE HOLE for 5 16 BOLT RAFTER D BASED ON 16 CENTER RAFTERS B B C C A DRILL POINTS CLEARANCE HOLE for...

Страница 17: ...SCREWS FENDER WASHER LOCK WASHER NUT ROOF RAFTER SPACER BLOCK Figure 16 Table 4 IF MOUNTING WITH AN OPTIONAL TILT MOUNT KIT FOR OPTIMAL COLLECTOR ANGLE REFER TO ITS INSTRUCTION SHEET FOR THE APPLICAB...

Страница 18: ...unting brackets prior to raising the collectors The collector can then be set on the lower mounting brack ets while the top clips are fastened over the lip on the collector frame 4 After the solar col...

Страница 19: ...spacing of collectors as attachment of piping is easiest with properly aligned collectors The connection between the collector panels is made with copper unions or couplings To aid in installation th...

Страница 20: ...ration Ensure that all roof penetrations required to plumb and mount the solar collector are properly flashed and sealed in accordance with standard roofing practices The return and supply lines shoul...

Страница 21: ...a com parable level of knowledge specialist The following must be observed during installation and start up Relevant local and national codes Accident prevention regulations of the professional associ...

Страница 22: ...HARGE LINE DRAIN VALVE CONNECTION SET WITH EXPANSION TANK Figure 22 6 Connect a discharge line to the pressure relief valve in the solar circuit 7 Connect the stainless steel corrugated hose to the sa...

Страница 23: ...ed to pump to the tank return threaded fitting Figure 25 FUNCTION Check valves The solar station is equipped with check valves in the supply and the return ball valve J Q For filling venting and flush...

Страница 24: ...priate drain 12 Turn the supply ball valve b to 90 horizontal so that the valve is closed 13 Turn on the supply water and open the fill valve d then leave running for 15 minutes to flush debris out of...

Страница 25: ...st the solar pump speed using the pump speed selector on the side of the pump f Set the speed to the lowest level possible to achieve the recommended system flow rate See Table 5 NUMBER OF COLLECTORS...

Страница 26: ...r loop pump upper primary and one for the water loop pump lower secondary Relay 1 primary pump 18 Line power R1 17 Neutral N 13 Ground Relay 2 secondary pump 16 Line power R2 15 Neutral N 14 Ground Th...

Страница 27: ...d button down for 2 seconds and the system setting screens can then be shown If an adjustable value is shown on the display is indicated To change the set value press the Set button 3 so that flashes...

Страница 28: ...quickly blinking if there is a sensor error Operation control lamp indication Constantly green system operation normal Red green blinking initialization phase manual operation Red blinking sensor err...

Страница 29: ...ssioning menu press button 3 The controller is now ready for operation with typical settings to suit the system layout The settings made in the commissioning menu can be changed later on in the corres...

Страница 30: ...e value for heat quantity will be set to 0 In order to finish the reset procedure the set button 3 must be pressed in order to confirm In order to interrupt the reset procedure no button should be pre...

Страница 31: ...ep If the temperature decreases the secondary pump will decrease by 1 step followed by the primary pump n1MN n2MN Minimum pump speed Adjustment range 30 to 100 Recommended setting 30 A relative minimu...

Страница 32: ...available when OCF is active CFRF Antifreeze temperature off Adjustment range 40 to 50 F Recommended setting 41 F Channel only available when OCF is active O TC Tube collector function Adjustment OFF...

Страница 33: ...MAN1 MAN2 as follows Operating mode OFF relay off flashing AUTO relay in automatic operation ON relay on flashing n1 2 LO minimum speed Note Always adjust the operating mode back to Auto when the cont...

Страница 34: ...valve in solar pump station Inspect valve and repair or replace Cold water supply dip tube Missing or defective Replace dip tube Collectors Absorber coating degradation Replace collector Collector pan...

Страница 35: ...er fuse Repair or replace Flow rated too high or too low Adjust flow rate Faulty pump Listen for irregular noises in pump operation Feel collector feed and return line for temperature difference Ensur...

Страница 36: ...tial set too low Reset off differential according to recommendation Controller set to on position Set system operation to Auto Pump operated but no fluid flows from collectors Air Scoop System air loc...

Страница 37: ...pressure drops unexpectedly contact your installation contractor immediately to diagnose the problem and recharge the system SOLAR PANEL CLARITY If you live in a dusty climate once a month wash off d...

Страница 38: ...Loop Dip Tube w Nipple 9006790005 12 Plastisert Nipple 9003976015 13 T P Valve 9000728015 14 Drain Valve 9003906015 SOLEX DWHX PUMP STATION SERVICE PARTS 15 Temperature Gauge Supply Red 9007789005 16...

Страница 39: ...l Protection Exposure Limits Component List Type Value Propylene glycol Personal Protection Eye Face Protection Use safety glasses Skin Protection Wear clean body covering clothing Hand protection Use...

Страница 40: ...40...

Отзывы: