Sprinkler Option Temperature Controller Settings
NOTE: Refer to Controller’s User’s Manual for further information on controller options.
Message
Display
Message
Description
Settings
SECr
SECURITY CODE
FULL SECURITY -
SET TO 110 (DISPLAYED AS 1) "VIEW ONLY"
NO SECURITY -
SET TO 111 (DISPLAYED AS 4)
"ALL FEATURES UNLOCKED"
InP
INPUT DEVICE
P 385 = RTD
INPUT
F-C
º F OR º C
SELECT TYPE REQUIRED
(FAHRENHEIT OR CELSIUS)
dPt
DECIMAL POINT
0, NO DECIMAL POINT
InPt
INPUT FAULT TIMER
0.2
SPL
SET POINT LOW
500
(SETTING
CANNOT BE
LOWER)
SPH
SET POINT HIGH
700
(SETTING
CANNOT BE
HIGHER)
SPSt
SET POINT STATE
rE
(REVERSE ACTION)
SPLP
SET POINT LAMP
0
o
FF
(LAMP OFF WHEN OUTPUT IS ON)
AL
HIGH ALARM ONLY
Hi
ALt
ALARM TYPE
Abs
(ABSOLUTE ALARM)
ALrE
ALARM RESET
OnOF
(AUTOMATIC RESET)
ALPi
ALARM POWER
INTERRUPT
OFF
(ALARM INHIBIT IS OFF)
ALiH
ALARM INHIBIT
OFF
(ALARM INHIBIT IS OFF)
ALSt
ALARM OUTPUT
STATE
CLOS
(CLOSES CONTACTS AT ALARM SET POINT)
ALLP
ALARM LAMP
0 ON
(ALARM LAMP IS ON WHEN ALARM CONTACT IS CLOSED)
ALHi
ALARM HI
575º F OR 301.6º C
(NOTE: ADJUST SAME AS SP)
Cy
CYCLE RATE
OnO F
SP_d
SET POINT ON-OFF
DIFFERENTIAL
-1
rt
RAMP TIME
OFF
InPC
INPUT CORRECTION
0
FiLt
DIGITAL FILTER
2
SP
TEMPERATURE
SET POINT
575º F OR 301.6º C
Note: When message display (Cy) set to OnOF.
SPOL (SET POINT OUTPUT LOW LIMIT) not in use.
SPOH (SET POINT OUTPUT HIGH LIMIT) not in use.
Are not displayed.
Содержание AD-310
Страница 11: ...7 310 NON TILT GAS MODEL B DIMENSIONS AND COMPONENT LOCATION ...
Страница 12: ...8 310 NON TILT STEAM MODEL ...
Страница 14: ...10 1 Reassembly Instructions For Gas Dryer Shipped In Two 2 Pieces ...
Страница 16: ...12 2 Reassembly Instructions For Steam Dryer Shipped In Two 2 Pieces ...
Страница 22: ...18 ...
Страница 23: ...19 ...
Страница 24: ...20 ...
Страница 64: ...60 B I O BOARD INPUT AND OUTPUT L E D INDICATORS ...
Страница 80: ...76 ...
Страница 81: ...ADC 113110 1 01 04 00 20 2 05 07 01 20 ...