Consistent gas pressure is essential at
ALL
gas connections. It is recommended that a 2-inch (5.08 cm)
pipe gas loop be installed in the supply line servicing a bank of dryers. An in-line pressure regulator
must be
installed in the gas supply line (header) if the (natural) gas pressure exceeds 12.0 inches (29.9 mb) of water
column (W.C.) pressure.
IMPORTANT:
A water column pressure of 3.5 inches (8.7 mb) for natural gas and 10.5 inches (26.1
mb) for liquid propane (L.P.) dryers is required at the gas valve pressure tap of each
dryer for proper and safe operation.
A 1/8-inch N.P.T. plugged tap, accessible for a test gauge connection,
must be
installed in the main gas
supply line immediately upstream of each dryer.
IMPORTANT:
Pipe joint compounds that resist the action of natural and L.P. gases
must be
used.
IMPORTANT:
Test
ALL
connections for leaks by brushing on a soapy water solution (liquid
detergent works well).
WARNING: NEVER
TEST
FOR
GAS
LEAKS
WITH
A
FLAME!!!
ALL
components/materials
must conform
to National Fuel Gas Code Specifications ANSI Z223.1-LATEST
EDITION, or in Canada, CAN/CGA-B149.1-M91 (Natural Gas) or CAN/CGA-B149.2-M91 (L.P. Gas) or
LATEST EDITION (for General Installation and Gas Plumbing), as well as local codes and ordinances and
must be
done by a qualified professional. It is important that gas pressure regulators meet applicable
pressure requirements, and that gas meters be rated for the total amount of
ALL
the appliance BTUs being
supplied
IMPORTANT:
The dryer and its individual shutoff valve
must be
disconnected from the gas supply
piping system during any pressure testing of that system at test pressures in excess of
1/2 psig (3.5 kPa).
NOTE:
The dryer
must be
isolated from the gas supply piping system by closing its individual manual
shutoff valve during any pressure testing of the gas supply piping system at test pressures
equal to or less than 1/2 psig (3.5 kPa).
H. WATER SUPPLY CONNECTION FOR OPTIONAL SPRINKLER SYSTEM
If the optional sprinkler system was purchased with the dryer, connect a 40-70 psig (276-483 kPa) supply of
water into the 1-inch F.P.T. sprinkler shutoff valve, which is located on top of the dryer on the left hand side.
Содержание AD-310
Страница 11: ...7 310 NON TILT GAS MODEL B DIMENSIONS AND COMPONENT LOCATION ...
Страница 12: ...8 310 NON TILT STEAM MODEL ...
Страница 14: ...10 1 Reassembly Instructions For Gas Dryer Shipped In Two 2 Pieces ...
Страница 16: ...12 2 Reassembly Instructions For Steam Dryer Shipped In Two 2 Pieces ...
Страница 22: ...18 ...
Страница 23: ...19 ...
Страница 24: ...20 ...
Страница 64: ...60 B I O BOARD INPUT AND OUTPUT L E D INDICATORS ...
Страница 80: ...76 ...
Страница 81: ...ADC 113110 1 01 04 00 20 2 05 07 01 20 ...