1.9 STO Input Wiring
The SV160E2-STO uses Inputs 3 and 4 as the redundant STO inputs. These inputs must have 12 to 24 Vdc
applied to them before the motor’s power stage is enabled. If you have an SV160E2-STO and are not using
the STO functionality, then you must apply 12 to 24Vdc to both inputs to bypass the STO functionality. Col-
ors in parentheses are the appropriate wire color for the CNFL-5M cable.
Figure T1.8 STO Input Connections
1.9.1 Extending the STO Cabling
The STO inputs are fast acting, and therefore susceptible to electrical noise. Keep the cabling from the safety
relay to the SV160E2-STO as short as possible. If you have to extend the cabling beyond a CNFL-5M, use
shielded twisted pair cabling. The second wire of the pair should be connected to the power supply return.
STOB
STOB
STOA
STOA
IN DC Common
IN DC Common
+
+
(YEL)
(YEL)
(GRN)
(GRN)
12 to
24 Vdc
12 to
24 Vdc
1.7.3
1.7.3
1.9.1
3
3
(BLU)
(BLU)
4
4
7
7
Содержание SV160E2
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0S252 E2 Technology...
Страница 10: ...ABOUT THIS MANUAL SV160E2 User Manual ADVANCED MICRO CONTROLS INC 10 Notes...
Страница 40: ...MOVE PROFILE CALCULATIONS SV160E2 User Manual ADVANCED MICRO CONTROLS INC 40 Notes...
Страница 56: ...CONFIGURATION MODE DATA FORMAT SV160E2 User Manual ADVANCED MICRO CONTROLS INC 56 Notes...
Страница 88: ...INSTALLING THE SV160E2 SV160E2 User Manual ADVANCED MICRO CONTROLS INC 88 Notes...
Страница 108: ...ETHERNET IP EXPLICIT MESSAGING SV160E2 User Manual ADVANCED MICRO CONTROLS INC 108 Notes...
Страница 112: ...MODBUS TCP CONFIGURATION SV160E2 User Manual ADVANCED MICRO CONTROLS INC 112 Notes...
Страница 120: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...