NR60E2 User Manual
ADVANCED MICRO CONTROLS INC.
42
3.3d Use the AMCI NET Configurator Utility (continued)
3.3d.8 Set the IP Address, Subnet Mask, and Default Gateway
Enter your desired values into the IP Address, Subnet Mask, and Default Gateway fields.
The Default Gateway setting is not optional! In order to comply with the ODVA specification,
it must be set to a valid address on the chosen subnet. Because the Default Gateway is often
not used in device level networks, if you do not have a required value for it, AMCI suggests
setting the Default Gateway to the IP address of your host controller.
If the IP Address Switches are set to any value within the range of 1 to 254, the last octet of the
IP address you program into the NET Configurator must match this value.
3.3d.9 Write the New IP Address to the NR60
Click on the [Set IP Address] button. If there is an error in the settings, the utility will tell you what is wrong.
Once there are all correct, the utility will write the new IP address settings to the NR60E2. These settings are
automatically saved to nonvolatile memory.
3.3d.10 Remove Power from the NR60
The new IP address will not be used until power to the NR60E2 has been cycled.
3.3d.11 Verify and Change the IP Address Switch Settings
If the IP Address Switches are set to any valid number between 1 and 254, the NR60E2 will use this number
for the last octet of the IP address on power up. For example:
You use the NET Configurator utility to program an address of 172.16.0.219.
The IP Address Switches are left at their factory default setting of 050.
The NR60E2 will power up with an address of 172.16.0.
50
, not 172.16.0.
219
.
Therefore, if needed, follow the
Use the NR60E2 IP Address Switches
procedure to set the IP Address
Switches to any value between 255 and 989. This procedure starts on page 35.
Do not set the IP Address Switches to a value of 000, as this will enable the DHCP client
on the NR60E2. If the DHCP client is enabled and a DHCP server is not available, the
NR60E2 will never receive an IP Address.
Address 990 through 999 are used by the factory when testing the unit. The IP Address
Switches should not be set within this range by customers in the field.
Содержание NR60E2
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual E2 Technology E2 Technology Manual 940 0D161...
Страница 6: ...TABLE OF CONTENTS NR60E2 User Manual ADVANCED MICRO CONTROLS INC 6 Notes...
Страница 20: ...NR60 SPECIFICATIONS NR60E2 User Manual ADVANCED MICRO CONTROLS INC 20 Notes...
Страница 44: ...PROTOCOL SPECIFIC INFORMATION NR60E2 User Manual ADVANCED MICRO CONTROLS INC 44 Notes...
Страница 52: ...IMPLICIT COMMUNICATIONS WITH AN EDS EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 52 Notes...
Страница 58: ...IMPLICIT COMMUNICATIONS WITHOUT EDS EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 58 Notes...
Страница 70: ...CIP POSITION SENSOR OBJECT EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 70 Notes...
Страница 90: ...PROFINET CYCLIC DATA FORMATS PROFINET Protocol ADVANCED MICRO CONTROLS INC 90 Notes...
Страница 98: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...