Transmit Bit
The
Transmit Bit
is used to tell the ANR2 when a new command is being written to it. Bit 15 of the Command
Word in the Network Output Data (Output Word 0, bit 15) is always the
Transmit Bit
.
The ANR2 only accepts commands when the Transmit bit makes a 0
1 transition. Therefore, this bit must
be reset between commands. The easiest way to do this is to write a value of zero into the Command Word
before writing the next command. Once this bit is reset, the ANR2 will respond by resetting the
Acknowledge
Bit
. At this point, another command can be written to the ANR2.
This condition also applies when switching between modes.
Entering Configuration Mode
The ANR2 will allow you to enter Configuration Mode after power up as long as valid Calibration data exists.
This is the normal operating condition of the module. If the ANR2 powers up with the
In Calibration Mode
and
Module Initialized
bits set to “1”, then the factory set calibration data has been corrupted. If this has
occurred, contact AMCI for assistance. See
starting on page 38 for a full
description of the
In Calibration Mode
and
Module Initialized
bits.
You can also enter Configuration Mode from Alignment Mode or Measurement Mode at any time by writing
the following data to the ANR2.
Figure 6.1 Enter Config Mode: Network Output Data
The ANR2 responds by setting the
Acknowledge
bit and the
In Configuration Mode
bits if the command was
accepted. It will respond with an error code of “0001”, Command Error, if the command was not accepted.
See
starting on page 38 for a full description of the response bits.
At this point, you must reset the
Transmit Bit
(Output Word 0, bit 15), before the ANR2 will accept another
command. The easiest way to do this is to write a value of zero into the Command Word. The ANR2 will
respond by resetting the
Acknowledge Bit
.
This chapter covers the format of the Network Output Data when the ANR2 is in
Configuration Mode. You will set Excitation Voltage parameters as well as sensor
sensitivity and displacement while in this mode.
ANR2
Word
Value
Description
0
16#A000
Command Word to enter Configuration Mode
1
16#1298
Password
2 – 9
16#0000
Not Used
Содержание ANR2
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0A032...
Страница 14: ...INTRODUCTION TO THE ANR2 ADVANCED MICRO CONTROLS INC 1 14 Notes...
Страница 18: ...OPERATING MODES ADVANCED MICRO CONTROLS INC 2 18 Notes...
Страница 32: ...INSTALLING THE ANR2 ADVANCED MICRO CONTROLS INC 3 32 Notes...
Страница 36: ...AMCI NET CONFIGURATOR SOFTWARE ADVANCED MICRO CONTROLS INC 4 36 Notes...
Страница 48: ...CONFIGURATION MODE DATA FORMAT ADVANCED MICRO CONTROLS INC 6 48 Notes...
Страница 58: ...ALIGNMENT MODE DATA FORMAT ADVANCED MICRO CONTROLS INC 7 58 Notes...