O
PERATING
M
ODES
ADVANCED MICRO CONTROLS INC.
2
16
Available Modes (continued)
Alignment Mode
After the module is configured, Alignment Mode is used to set the Minimum, Maximum, and Null Values.
Note that each channel is programmed separately
† The Null Value is not set when using the Two Point Linear method. When using this method, the maxi-
mum distance between the Minimum Value and Maximum Value is 65,535 counts. Both values must be in
the range of ±2,147,483,647.
Table 2.2 Alignment Parameters
Measurement Mode
After the sensor is aligned, use Measurement Mode to read back the position and velocity values from your
sensor. If the ANR2 automatically enters Measurement Mode after you exit a different mode, you must issue
a command to the unit to tell it which channels to read.
Status Bits
The ANR2 has five module status bits so you can determine the state of the module. It also has four status
bits per channel to tell you what valid data exists for the channel and if the ANR2 is actively measuring the
position of the sensor.
Module Status Bits
Module Initialized:
This bit is set on power up or after a hardware reset. The ANR2 is only transmitting status
information. Position data is set to zero. The module is waiting for the first command from the host
controller.
In Calibration Mode:
If this bit is set along with the
Module Initialized
bit on power up, the ANR2 requires cal-
ibration. If it is set when the
Module Initialized
bit is reset, the unit is in Calibration Mode.
In Configuration Mode:
If this bit is set along with the
Module Initialized
bit on power up, the ANR2 does not
have valid configuration data for either channel. If it is set when the
Module Initialized
bit is reset, the
unit is in Configuration Mode. Use the Channel Status bits to determine which channels require con-
figuration.
In Alignment Mode:
If this bit is set along with the
Module Initialized
bit on power up, the ANR2 does not
have valid alignment data for either channel. If it is set when the
Module Initialized
bit is reset, the
unit is in Alignment Mode. Use the Channel Status bits to determine which channels require align-
ment.
In Measurement Mode:
If this bit is set along with the
Module Initialized
bit on power up, the ANR2 is ready
to measure position on at least one of the channels. If it is set when the
Module Initialized
bit is reset,
the unit is in Measurement Mode. Use the Channel Status bits to determine which channels the
ANR2 is actively measuring.
Channel Status Bits
Channel Calibrated:
Valid calibration data exists for the channel.
Channel Configured:
Valid configuration data exists for the channel.
Channel Aligned:
Valid alignment data exists for the channel.
Channel Measuring:
The ANR2 is actively measuring the position of the sensor.
Parameter
Range
Units
Null Value
†
±2,147,483,647
Counts
Minimum Value
Null Position ± 65,535
±2,147,483,647 max.
Counts
Maximum Value
Null Position ± 65,535
±2,147,483,647 max.
Counts
Содержание ANR2
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0A032...
Страница 14: ...INTRODUCTION TO THE ANR2 ADVANCED MICRO CONTROLS INC 1 14 Notes...
Страница 18: ...OPERATING MODES ADVANCED MICRO CONTROLS INC 2 18 Notes...
Страница 32: ...INSTALLING THE ANR2 ADVANCED MICRO CONTROLS INC 3 32 Notes...
Страница 36: ...AMCI NET CONFIGURATOR SOFTWARE ADVANCED MICRO CONTROLS INC 4 36 Notes...
Страница 48: ...CONFIGURATION MODE DATA FORMAT ADVANCED MICRO CONTROLS INC 6 48 Notes...
Страница 58: ...ALIGNMENT MODE DATA FORMAT ADVANCED MICRO CONTROLS INC 7 58 Notes...