Front Panel (continued)
Excitation Mode Jumper
Figure 1.6 shows the location of the headers that set the excita-
tion mode of the ANR2. You access the headers by opening the
front cover of the module. All ANR2 modules ship with a
jumper across the “Master” pins. To set the module to slave
mode, move the jumper from the Master pins to the Slave pins.
The module will not operate correctly if the
jumper is not across one of the sets of pins.
Jumper these two pins
for a Master Module.
(Factory Default)
Jumper these two pins
for a Slave Module.
Figure 1.6 Slave Mode Jumper Location
Specifications
Sensor Type
AC. Half bridge, three, four, five, or six wire
LVDT/RVDT.
Number of Input Channels
Two
Number of I/O Words (16 bits each)
10 input words and 10 output words
Physical Dimensions
Width: 0.9 inches max.
Depth: 4.5 inches max.
Height: 3.9 inches
5.0 inches min. with mating connectors
Weight
0.38 lbs. (0.17 kg.) with mating connectors
Current Draw
200 mA without sensors
375 mA with Excitation voltage shorted to GND.
Available Measurement Methods
Differential and Ratiometric. Ratiometric is only
available as an option with 5- and 6- wire sen-
sors.
Excitation Voltage
Voltage Output:
Programmable from 0.800 to 12.000 Vrms
with 1 millivolt resolution
Frequency:
Programmable from 400 to 10,000 Hz
with 1 Hz resolution
Output Current:
200 mA maximum
Sensor Sensitivity
Programmable from 0.1 to 5,000.0 mV/V/{mm,
0.001" (mil), 0.01°} with a resolution of 0.1 mV.
The ANR2 uses Sensor Sensitivity and Sensor
Displacement to set input amplifier gains.
Sensor Displacement
Programmable from 5 to 10,000. Units are
0.01mm, 0.001" (mil), or 0.01°. Distance units
must match units used when programming Sen-
sor Sensitivity. The ANR2 uses Sensor Sensi-
tivity and Sensor Displacement to set input
amplifier gains.
Position Resolution
14 bit max. (16,384 steps over entire range) Posi-
tion output can be scaled to a 32 bit value
Position Update Time
250 microseconds.
Environmental Specifications
Input Power ...... 24 Vdc ±10%, surge to 30Vdc
without damage to module.
Ambient Operating Temperature
........... -4° to 122°F (-20° to 50°C)
Storage Temperature
........... -40° to 185°F (-40° to 85°C)
Humidity ........... 0 to 95%, non-condensing
Status LED
starting on page 12.
Connectors
Mating connectors are included with the ANR2
and are available separately under the following
AMCI part numbers.
Connector
AMCI Part #
Wire
Strip Length
Min. Tightening Torque
I/O
MS-2X11
28 - 16 AWG
0.275 inches
Spring Cage Connector
Power
MS-4M
28 - 12 AWG
0.394 inches
4.43lb-in (0.5 Nm)
Backplane
IC-5
Not Applicable
Содержание ANR2
Страница 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual Manual 940 0A032...
Страница 14: ...INTRODUCTION TO THE ANR2 ADVANCED MICRO CONTROLS INC 1 14 Notes...
Страница 18: ...OPERATING MODES ADVANCED MICRO CONTROLS INC 2 18 Notes...
Страница 32: ...INSTALLING THE ANR2 ADVANCED MICRO CONTROLS INC 3 32 Notes...
Страница 36: ...AMCI NET CONFIGURATOR SOFTWARE ADVANCED MICRO CONTROLS INC 4 36 Notes...
Страница 48: ...CONFIGURATION MODE DATA FORMAT ADVANCED MICRO CONTROLS INC 6 48 Notes...
Страница 58: ...ALIGNMENT MODE DATA FORMAT ADVANCED MICRO CONTROLS INC 7 58 Notes...