MicroLogix 1500 & CompactLogix Resolver Module
Revision 2.1
Limit Switch Data
Output Being Programmed: This parameter defines to what output the remaining Limit Switch setup
parameters are being assigned to.
2611-13 module range: 0 to 15
2612-13 module range: 0 to 23
2613-13 module range: 0 to 31
Limit Offset: Each of the 2600-13 modules outputs fires based on its own internal position, which may or
may not be equal to the Scaled Machine Position. The Limit Offset parameter is added to this
internal position adjusting where the On/Off setpoints fire. Please note that a positive Limit
Offset causes the output to turn on earlier and a negative Limit Offset causes the output to turn
on later.
This parameter has a range of (–Rollover Position to + Rollover Position)
The factory default value is 0.
Output Setpoint: Each of the 2600-13 modules outputs can be programmed with 16 on / off setpoints. This
parameter defines which of these 16 on/off setpoint is being programmed with the current
block of data.
This parameter has a range of 0 to 15
From Position: This parameter defines the resolver position where the Output Position will turn on.
This parameter has a range of (
0 to Resolver Rollover Position
)
To Position: This parameter defines the resolver position where the Output Position will turn off.
This parameter has a range of (
0 to Resolver Rollover Position
)
The Limit Switch Output will be on for the entire rotation of the resolver if
the From and To setpoints are equal to each other.