5.10
Relay PI control integral high limit value
Section:
AL 1
to
AL 8
Display:
I.H
Range:
0
to
100.0
%
Default Value:
0.000
Default Access Level
4
Function number
4240
to
4247
Allow the relay PI control integral high limit to be set, refer to “Setting up the relay PI control” chapter in the
Addendum booklet.
5.11
Relay PI control integral low limit value
Section:
AL 1
to
AL 8
Display:
I.L
Range:
0
to
100.0
%
Default Value:
100.0
Default Access Level
4
Function number
4250
to
4257
Allow the relay PI control integral low limit to be set, refer to “Setting up the relay PI control” chapter in the
Addendum booklet.
5.12
Relay PI control bias
Section:
AL 1
to
AL 8
Display:
biAS
Range:
0
to
100.0
%
Default Value:
50.0
Default Access Level
4
Function number
4260
to
4267
Allow the relay PI control bias to be set, refer to “Setting up the relay PI control” chapter in the Addendum book-
let.
5.13
Relay PI control duty cycle
Section:
AL 1
to
AL 8
Display:
dutY SECS
Range:
0
to
6553.5
secs
Default Value:
10.0
Default Access Level
4
Function number
4270
to
4277
Allows the relay PI control duty cycle to be set, refer to “Setting up the relay PI control” chapter in the Addendum
booklet.
34 of