![AMALGAMATED INSTRUMENT LD5-RS Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/amalgamated-instrument/ld5-rs/ld5-rs_operation-and-instruction-manual_2915959021.webp)
RO 1
to
RO 2
InPt
Analog retransmission input channel
(
∗
Optional)
Any available
channel
CH1
Addendum
RO 1
to
RO 2
P.CtI
Analog output PI control (
∗
Optional)
NO
or
YES
No
Addendum
RO 1
to
RO 2
SEtP
Analog output PI control setpoint
(
∗
Optional)
Any display value
0
Addendum
RO 1
to
RO 2
SPAn
Analog output PI control span
(
∗
Optional)
Any display value
1000
Addendum
RO 1
to
RO 2
P.g
Analog output PI control proportional
gain (
∗
Optional)
Any display value
1.000
Addendum
RO 1
to
RO 2
I.g
Analog output PI control integral gain
(
∗
Optional)
Any display value
0.000
Addendum
RO 1
to
RO 2
I.H
Analog output PI control integral high
limit (
∗
Optional)
0
to
100.0
%
100.0
Addendum
RO 1
to
RO 2
I.L
Analog output PI control integral low
limit (
∗
Optional)
0
to
100.0
%
100.0
Addendum
RO 1
to
RO 2
biAS
Analog output PI control bias
(
∗
Optional)
0
to
100.0
%
50.0
Addendum
RO 1
to
RO 2
Lo
Analog retransmission low display
value (
∗
Optional)
Any display value
0
Addendum
RO 1
to
RO 2
High
Analog retransmission high display
value (
∗
Optional)
Any display value
1000
Addendum
4.6
Input setup function table
Display
Function
Range
Default
Your
record
Ref/Page
IN 1
C.SUM
Checksum error detection
OFF
or
ON
On
/
IN 1
SCH1
Serial input address character 1
-2
to
255
-1
/
IN 1
SCH2
Serial input address character 2
-2
to
255
-1
/
IN 1
SCH3
Serial input address character 3
-2
to
255
-1
/
IN 1
SCH4
Serial input address character 4
-2
to
255
-1
/
LD5RSMAN-2.0-0
21 of