Explanation of functions
The setup and calibration functions are configured through a push button sequence. The push buttons located at the
front of the instrument or on the main circuit board are used to alter settings.
Display messages shown are those which would appear on a display with 4 digits for the process reading, these
display messages may in some cases vary slightly for other display types.
Note: default access levels for each function are shown in this section but the access levels are not applicable to this
software version.
Explanation of Functions
5.1
Alarm relay high setpoint
Section:
AL 1
to
AL 8
Display:
High
Range:
Any display value or
OFF
Default Value:
OFF
Default Access Level
2
Function number
4000
to
4007
Displays and sets the high setpoint value for the designated alarm relay. Use this high setpoint function if a relay
operation is required when the display value becomes equal to or more than the low setpoint value.
To set the high alarm value go to the
High
function, press
F
and when you see a digit of the value flash use
the
^
or
v
push buttons to set the required value then press
F
to accept this selection. The high alarm setpoint
may be disabled by pressing the
^
and
v
push buttons simultaneously. When the alarm is disabled the display
will indicate
OFF
. If the relay is allocated both a low and high setpoint then the relay will activate when the value
displayed moves outside the band set by the low and high setpoints. The value at which the relay will reset is
controlled by the
HYSt
function.
Overlapping alarms - if the
HiGh
value is set lower than the
Lo
value then the alarm will activate in the band
between the two values.
If the display has annunciator leds for the relay then the annunciator will initially flash in alarm condition, if the
alarm is acknowledged by pressing the
F
button (where fitted) or has been acknowledged by a
P
button or remote
input operation the annunciator will be solidly lit until the display moves out of alarm condition.
Example:
If
High
under
AL 1
is set to
100
then relay 1 will activate when the display value is
100
or higher.
30 of
LD5RSMAN-2.0-0