eFlow104N Series Installation Guide

NEC Power-Limited Wiring Requirements for eFlow104NX Models:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit 

wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited 

circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. 

One such example of this is shown below. Your specific application may require different conduit knockouts to 

be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field 

wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).

Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods.

For Canadian installations use shielded wiring for all connections.

Note:

 Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire 

(Fig. 8a).

Fig. 8

Fig. 8a

*  Outputs are non power-limited:

  eFlow104NX, eFlow104NX8, eFlow104NX16.

  Outputs are Class 2 power-limited:

  eFlow104NX8D, eFlow104NX16D.

Input 120VAC 

60Hz

(non power-

limited)

Optional UL 

Listed

Battery 

Enclosure

(non power-

limited)

Supervisory, Fire Alarm Interface

and Aux. output Connections

(power-limited)

Battery Connections

(non power-limited)

DC Output*

Power

Distribution

External

Jacketed

Shield

Incorrect Wire

Handling

Correct Wire

Handling

Pull back

external jacketed

shield approx. 1/2”.

Wire

Insulation

Solid Copper

Conductors

Содержание eFlow104N Series

Страница 1: ...t 8 PTC Protected Class 2 Power Limited Outputs eFlow104N16D eFlow104NX16D 10A 24VDC Sixteen 16 PTC Protected Class 2 Power Limited Outputs eFlow104N Series Power Supply Chargers Models Include Rev 10...

Страница 2: ...104NX eFlow104N8 eFlow104NX8 eFlow104N16 and eFlow104NX16 The following units provide Class 2 power limited outputs eFlow104N8D eFlow104NX8D eFlow104N16D and eFlow104NX16D If a power limited output is...

Страница 3: ...60Hz Input Battery Wires Minimum 0 25 spacing must be provided CAUTION Do not touch exposed metal parts Shut branch circuit power before installing or servicing equipment There are no user serviceabl...

Страница 4: ...position Fig 1c pg 5 9 Trigger terminals are end of a line resistor supervised 10k ohms Opening or shorting trigger terminals will cause DC output to shutdown Fig 1d pg 5 10 Place a jumper for non lat...

Страница 5: ...power is present Contact rating 1A 30VDC A removed battery is reported within 5 minutes Battery reconnection is reported within 1 minute power limited Fig 1b pg 5 BAT Stand by battery connections Maxi...

Страница 6: ...Power Limited Outputs N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs From Power Supply Board Factory Install...

Страница 7: ...294 Applications Note 12V batteries are required for UL603 UL1481 and Canadian installations CAUTION Power supply board is factory set for 24VDC Use two 2 12VDC stand by batteries Keep power limited w...

Страница 8: ...employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian ins...

Страница 9: ...minimum 0 25 spacing 12AH Rechargeable batteries are the largest batteries that can fit in this enclosure A UL listed external battery enclosure must be used if using 40AH or 65AH batteries Optional...

Страница 10: ...employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian inst...

Страница 11: ...x 82 6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1...

Страница 12: ...25 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm...

Страница 13: ...ectric w 135o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelect...

Страница 14: ...emote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output...

Страница 15: ...ltronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warra...

Страница 16: ...5AH 6A 10A 1 5A 10A Over 4 Hours 10A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 0A Automatic switch over to stand by battery when AC fails Tran...

Отзывы: