eFlow104N Series Installation Guide 

- 5 -

Terminal Identification:

Power Supply/Charger

Terminal Legend

Function/Description

L, N

Connect 120VAC 60Hz to these terminals: L to hot, N to neutral (non power-limited) 

(Fig. 1a, pg. 5)

.

– DC +

24VDC nominal @ 10A continuous output (power-limited output) 

(Fig. 1h, pg. 5)

.

Trigger EOL

Supervised

Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open, 

normally closed from an FACP output circuit (power-limited input) 

(Fig. 1d, pg. 5)

.

NO, GND RESET

FACP interface latching or non-latching (power-limited) 

(Fig. 1e, pg. 5)

.

+ AUX –

Auxiliary Class 2 power-limited output rated @ 1A (unswitched) 

(Fig. 1f, pg. 5)

.

AC Fail 

NC, C, NO

Indicates loss of AC power, e.g. connect to audible device or alarm panel. 

Relay normally energized when AC power is present. 

Contact rating 1A @ 30VDC (power-limited) 

(Fig. 1b, pg. 5)

.

Bat Fail

NC, C, NO

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized 

when DC power is present. Contact rating 1A @ 30VDC. 

A removed battery is reported within 5 minutes.

Battery reconnection is reported within 1 minute (power-limited) 

(Fig. 1b, pg. 5)

.

– BAT +

Stand-by battery connections. Maximum charge current 1.0A (non power-limited)

(Fig. 1g, pg. 5)

.

Power Distribution Module

Terminal Legend PD8UL/PD8ULCB

Terminal Legend PD16W/PD16WCB Function/Description

1P to 8P

1P to 16P

Positive DC power outputs.

1N to 8N

1N to 16N

Negative DC power outputs.

Fig. 1 - 

eFlow104N Board Configuration

1a

1b

1g

1h

1e 1f

1d

1c

–   DC   

+

–   BAT   

+

L         G          N

NC     C     NO    NC     C      NO  

AC FAIL

BAT FAIL

TRIGGER EOL

SUPERVISED

AC DC

AC1

NO GND

RESET

+ AUX -

1 min   enable
2 hr      disable

––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––

Trouble/Time Limited Warning of Stand-by Batteries:

For compliance with ULC S318-96, the Time Limited Warning circuit must be connected for local or remote annun-

ciation with an Amber or Red LED to indicate DC Trouble (low battery, loss of battery or when 95% of the stand-by 

battery has been depleted). Connect the circuit to the Batt Fail relay contacts to an appropriate input of a UL Listed 

Burglar Alarm or Access Control Panel. The following figure shows the circuitry needed for local annunciation.

Содержание eFlow104N Series

Страница 1: ...t 8 PTC Protected Class 2 Power Limited Outputs eFlow104N16D eFlow104NX16D 10A 24VDC Sixteen 16 PTC Protected Class 2 Power Limited Outputs eFlow104N Series Power Supply Chargers Models Include Rev 10...

Страница 2: ...104NX eFlow104N8 eFlow104NX8 eFlow104N16 and eFlow104NX16 The following units provide Class 2 power limited outputs eFlow104N8D eFlow104NX8D eFlow104N16D and eFlow104NX16D If a power limited output is...

Страница 3: ...60Hz Input Battery Wires Minimum 0 25 spacing must be provided CAUTION Do not touch exposed metal parts Shut branch circuit power before installing or servicing equipment There are no user serviceabl...

Страница 4: ...position Fig 1c pg 5 9 Trigger terminals are end of a line resistor supervised 10k ohms Opening or shorting trigger terminals will cause DC output to shutdown Fig 1d pg 5 10 Place a jumper for non lat...

Страница 5: ...power is present Contact rating 1A 30VDC A removed battery is reported within 5 minutes Battery reconnection is reported within 1 minute power limited Fig 1b pg 5 BAT Stand by battery connections Maxi...

Страница 6: ...Power Limited Outputs N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs From Power Supply Board Factory Install...

Страница 7: ...294 Applications Note 12V batteries are required for UL603 UL1481 and Canadian installations CAUTION Power supply board is factory set for 24VDC Use two 2 12VDC stand by batteries Keep power limited w...

Страница 8: ...employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian ins...

Страница 9: ...minimum 0 25 spacing 12AH Rechargeable batteries are the largest batteries that can fit in this enclosure A UL listed external battery enclosure must be used if using 40AH or 65AH batteries Optional...

Страница 10: ...employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian inst...

Страница 11: ...x 82 6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1...

Страница 12: ...25 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm...

Страница 13: ...ectric w 135o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelect...

Страница 14: ...emote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output...

Страница 15: ...ltronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warra...

Страница 16: ...5AH 6A 10A 1 5A 10A Over 4 Hours 10A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 0A Automatic switch over to stand by battery when AC fails Tran...

Отзывы: