BATTERY BACKED POWER SUPPLY

 

RIP-12 mod.14 

(RIP-12-2/7P2-R) 

 

INSTRUCTION MANUAL 

1

 

TECHNICAL DATA 

1.1

 

General 

1.1.1

 

The  battery  backed  power  supply  RIP-12  mod.14  (RIP-12-2/7P2-R)  (hereinafter 

referred  to  as  the  RIP)  is  intended  to  provide  continuous  operating  power  to  a  group  of 
detectors  and  control  and  indicating  equipment  in  fire  alarm  systems,  security  systems, 
access control systems as well as to other appliances that require backed power of 12 V dc. 

1.1.2

 

The RIP provides round-the-clock operation with specified output parameters and 

automatic monitoring and recharging of the sealed backup battery (hereinafter referred to as 
the battery). The RIP provides shutting off the battery from a load to avoid its unacceptable 
discharge

.

 

1.1.3

 

The  RIP  provides  protecting  its  output  against  short  circuit  failures  with 

recovering  output  voltage  automatically  after  repairing  the  failures  as  well  as  protection 
against output overvoltage. 

1.1.4

 

The RIP provides protection against short circuit failures of battery leads keeping 

the output voltage stable if the RIP operates from mains power. 

1.1.5

 

The  RIP  provides  light  and  sound  indication  of  current  conditions,  including 

presence or absence of mains power voltage, the battery charge, a short circuit failure or an 
overload at the output, missed battery, shutting the battery off in case of its discharge as well 
as indication of possible RIP faults during operation (see Table 2). 

1.1.6

 

The RIP provides limiting of the battery charger voltage and current depending on 

the temperature within the device enclosure. 

1.1.7

 

The  RIP  provides  monitoring  battery  conditions  and  its  connecting  circuit  (by 

comparing with maximum admissible internal resistance of this circuit). 

1.1.8

 

The  RIP  design  does  not  imply  using  this  power  supply  in  explosion-hazardous 

premises. 

1.1.9

 

In  terms  of  environmental  conditions,  the  RIP  complies  with  the  climatic 

modification  ‘

УХЛ

’  (NF,  for  temperate  and  frigid  climate  zones)  and  the  arrangement 

category  3  as  per  GOST 15150-69  but  for  operation  at  the  temperature  range  263 ÷ 313 

К

 

(minus 10 t40°

С

) and relative humidity up to 90 % at 298 

К

 (+25 °

С

). 

1.1.10

 

In terms of resistance to mechanical exposure, the RIP meets the requirements of 

the arrangement group ‘LX’ as per GOST 12997-84 withstanding vibrations in the frequency 
range 1 through 35 Hz at 4.9 m/s

2

 (0.5 g) acceleration. 

1.2

 

Specifications 

1.2.1

 

The main power supply is the mains power 150 V to 250 V, 50 Hz. 

1.2.2

 

The  backup  power  supply*  is  a  Delta  battery  DTM1207  (12 V,  7 Ah)  or  similar 

one with equivalent parameters (with battery life at least 5 years). 

 

*

The battery to be supplied separately.

 

1.2.3

 

The rated output voltage while powered by mains is (13.6

±

0.6) V. 

1.2.4

 

The low battery shutdown voltage is (10.2

±

0.6) V. 

1.2.5

 

The rated load current is 2 A. 

Содержание RIP-12

Страница 1: ...t missed battery shutting the battery off in case of its discharge as well as indication of possible RIP faults during operation see Table 2 1 1 6 The RIP provides limiting of the battery charger voltage and current depending on the temperature within the device enclosure 1 1 7 The RIP provides monitoring battery conditions and its connecting circuit by comparing with maximum admissible internal r...

Страница 2: ...messages closed open state of the circuits is at least 3 s The time of delay for messages sent by the relays К1 К3 is 3 s The time of delay for messages Battery Low sent by the K2 relay does not exceed 1 min States of the solid state relay circuits are shown in Table 1 Table 1 Circuit Purpose Contact State К1 Output voltage monitoring In case of normal output voltage1 the contact is closed In case...

Страница 3: ...7 Package 1 pc no battery is included into the delivery 2 OPERATING INSTRUCTIONS 2 1 Safety Precautions 2 1 1 The current carrying circuits connected with mains power 220 V are a source of potential hazard These circuits are covered by a protective housing on the RIP printed circuit board 2 1 2 The safety precautions are as follows 1 The fuse shall always be good and its rating shall be as stated ...

Страница 4: ...n areas of the wires to be connected to the RIP 1 To connect the RIP to mains power 220 V the XT3 terminal block 0 75 2 5 mm2 for stranded wires or 1 2 mm in diameter for solid wires 2 To connect the load 0 5 2 5 mm2 for stranded wires or 0 8 2 mm in diameter for solid wires taking into account the maximum voltage drop on wires at maximum load current the minimum allowable voltage at the load 2 2 ...

Страница 5: ...nutes Operability of the battery charger at least once per 15 minutes Presence of mains voltage No overload and no short circuit conditions at the output 2 4 3 If no mains power is applied then the load starts to be powered by the battery the buzzer periodically emitting low battery warning beeps the POWER LED being off and the BAT LED and 12 V LED illuminating 2 4 4 If the battery voltage has dro...

Страница 6: ...2 Current Conditions of the RIP Indicators Buzzer POWER BAT 12 V TROUBLE green green green amber 1 Mains utility power is starting up no battery is connected ON 0 4 s 8 times 2 Mains power is OK the battery is nor charged OFF 3 s 3 Mains power is OK the battery is charged 4 DC output overcurrent The battery is available ON 15 60 s 2 Hz ON 1 5 s 2 times 5 Mains power is off the battery voltage exce...

Страница 7: ...aking into account the technical guide Maintenance of fire alarm systems and public address and general alarm systems of Types 1 2 in Orion ISS developed by the NVP Bolid Company 4 TROUBLESHOOTING N o Symptom Cause Action 1 The RIP fails to be turned on the mains power is on 1 Blown fuse F1 2 Faulty wiring 3 Long duration overload at the RIP DC output 1 Check the mains power voltage at the ХТ3 ter...

Страница 8: ...13 В 00703 6 2 RIP 12 mod 14 RIP 12 2 7P2 R Battery Backed Power Supply meets the requirements of Technical Regulations of Custom Union TR CU 004 2011 TR CU 020 2011 and is covered by Conformity Declaration ЕАЭС RU Д RU МЛ66 В 02301 6 3 RIP 12 mod 14 RIP 12 2 7P2 R is covered by the certificates of conformity of transport safety technical arrangements with their functional properties No МВД РФ 03 ...

Отзывы: