background image

 

7

2.5

 

Turning the RIP Off 

2.5.1

 

Turn off the mains power 220 V. 

2.5.2

 

Take the F1 fuse out. 

2.5.3

 

Disconnect the battery. 

3

 

MAINTENANCE 

The RIP shall be maintained according to a scheduled-preventive system which provides 

annual service. Maintenance works are to be performed by a service company employee and 
include: 

1)

 

Inspection of exterior condition of the RIP; 

2)

 

Checking the output voltage (with the load being connected to the RIP) in accordance 

with Section 1.2.3 of this Manual and checking the output voltage when the RIP is powered 
by the battery; 

3)

 

Checking operation of the light indicators in line with Table 2 of this Manual; 

4)

 

Verifying the RIP for secure mounting, wire conditions, and contact conditions; 

5)

 

Replacing the battery in proper time (when necessary but at least once per 5 years). 

Maintenance of fire alarm systems and public address / general alarm systems of the types 

1-2 comprising the RIP-12 mod.14 (RIP-12-2/7P2-R) is to be arranged taking into account the 
technical  guide  “Maintenance  of  fire  alarm  systems  and  public  address  and  general  alarm 
systems of Types 1-2 in Orion ISS” developed by the NVP Bolid Company. 

4

 

TROUBLESHOOTING 

N

Symptom 

Cause 

Action 

The RIP fails to be 
turned on, the mains 
power is on 

1. Blown fuse F1. 
2. Faulty wiring 
3. Long-duration overload 
at the RIP DC output 

1. Check the mains power voltage 
at the 

ХТ

3 terminal block before 

the F1 fuse and after it; replace the 
F1 fuse. 
2. Repair the wiring. 

3. Shut down the RIP. Wait for at 
least 2 min and then turn the RIP 
on again

.

 

The RIP fails to be 
turned on being powered 
by battery 

The battery voltage has 
dropped below 10 V 

Measure the battery voltage, 
charge or replace the battery 

The TROUBLE indicator 
blinks 

Overload or short circuit 
failure at the RIP output 

Check the current consumed by 
load. Rectify the overload / clear 
the short circuit 

The TROUBLE and BAT 
indicators blink 

1. The battery leads are 
corroded or connections 
between the battery leads 
and wire terminals are 
loosened. 
2. The battery has essentially 
lost its capacity 

1. Inspect the battery leads and 
clean them if necessary. 

2. Replace the battery 

Содержание RIP-12

Страница 1: ...t missed battery shutting the battery off in case of its discharge as well as indication of possible RIP faults during operation see Table 2 1 1 6 The RIP provides limiting of the battery charger voltage and current depending on the temperature within the device enclosure 1 1 7 The RIP provides monitoring battery conditions and its connecting circuit by comparing with maximum admissible internal r...

Страница 2: ...messages closed open state of the circuits is at least 3 s The time of delay for messages sent by the relays К1 К3 is 3 s The time of delay for messages Battery Low sent by the K2 relay does not exceed 1 min States of the solid state relay circuits are shown in Table 1 Table 1 Circuit Purpose Contact State К1 Output voltage monitoring In case of normal output voltage1 the contact is closed In case...

Страница 3: ...7 Package 1 pc no battery is included into the delivery 2 OPERATING INSTRUCTIONS 2 1 Safety Precautions 2 1 1 The current carrying circuits connected with mains power 220 V are a source of potential hazard These circuits are covered by a protective housing on the RIP printed circuit board 2 1 2 The safety precautions are as follows 1 The fuse shall always be good and its rating shall be as stated ...

Страница 4: ...n areas of the wires to be connected to the RIP 1 To connect the RIP to mains power 220 V the XT3 terminal block 0 75 2 5 mm2 for stranded wires or 1 2 mm in diameter for solid wires 2 To connect the load 0 5 2 5 mm2 for stranded wires or 0 8 2 mm in diameter for solid wires taking into account the maximum voltage drop on wires at maximum load current the minimum allowable voltage at the load 2 2 ...

Страница 5: ...nutes Operability of the battery charger at least once per 15 minutes Presence of mains voltage No overload and no short circuit conditions at the output 2 4 3 If no mains power is applied then the load starts to be powered by the battery the buzzer periodically emitting low battery warning beeps the POWER LED being off and the BAT LED and 12 V LED illuminating 2 4 4 If the battery voltage has dro...

Страница 6: ...2 Current Conditions of the RIP Indicators Buzzer POWER BAT 12 V TROUBLE green green green amber 1 Mains utility power is starting up no battery is connected ON 0 4 s 8 times 2 Mains power is OK the battery is nor charged OFF 3 s 3 Mains power is OK the battery is charged 4 DC output overcurrent The battery is available ON 15 60 s 2 Hz ON 1 5 s 2 times 5 Mains power is off the battery voltage exce...

Страница 7: ...aking into account the technical guide Maintenance of fire alarm systems and public address and general alarm systems of Types 1 2 in Orion ISS developed by the NVP Bolid Company 4 TROUBLESHOOTING N o Symptom Cause Action 1 The RIP fails to be turned on the mains power is on 1 Blown fuse F1 2 Faulty wiring 3 Long duration overload at the RIP DC output 1 Check the mains power voltage at the ХТ3 ter...

Страница 8: ...13 В 00703 6 2 RIP 12 mod 14 RIP 12 2 7P2 R Battery Backed Power Supply meets the requirements of Technical Regulations of Custom Union TR CU 004 2011 TR CU 020 2011 and is covered by Conformity Declaration ЕАЭС RU Д RU МЛ66 В 02301 6 3 RIP 12 mod 14 RIP 12 2 7P2 R is covered by the certificates of conformity of transport safety technical arrangements with their functional properties No МВД РФ 03 ...

Отзывы: