- 4 - 

eFlow104N Series Installation Guide

3.  Measure output voltage before connecting devices. This helps avoiding potential damage.

4.  Connect devices to be powered:

 

a.  For eFlow104N/eFlow104NX connect devices to terminals marked [– DC +] (

Fig. 1h, pg. 5

). 

 

b.  For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 8 marked  

 

  [1P & 1N] through [8P & 8N] 

(Fig. 3a & 3b, pg. 6) 

or 1 to 16 marked [1P & 1N] through [16P & 16N]

 

  (Fig. 4a & 4b, pg. 6)

 carefully observing correct polarity.

 

For auxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm 

 

Interface. Connect device to terminals marked [+ AUX –] 

(Fig. 1f, pg. 5).

5.  For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 

 

in the loss of the output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel 

 

type. Connect battery to terminals marked [– BAT +] 

(Fig. 1g, pg. 5)

. Use two (2) 12VDC batteries connected 

 

in series for 24VDC operation (battery leads included) Use batteries - Casil CL1270 (12V/7AH), 

 

CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 

 

batteries of an appropriate rating.

6.  Connect appropriate signaling notification devices to AC FAIL & BAT FAIL 

(Fig. 1b, pg. 5)

 supervisory relay outputs.

7.  To delay AC reporting for 2 hrs. set DIP switch [AC Delay] to OFF position 

(Fig. 1c, pg. 5)

.

 

To delay AC reporting for 1 min. set DIP switch [AC Delay] to ON position 

(Fig. 1c, pg. 5)

.

 

Note: 

Must be set to ON position for Burglar Alarm Applications.

8.  To enable Fire Alarm Disconnect set DIP switch [Shutdown] to ON position 

(Fig. 1c, pg. 5)

.

 

To disable Fire Alarm Disconnect set DIP switch [Shutdown] to OFF position 

(Fig. 1c, pg. 5)

.

9.  Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals 

 

will cause [DC] output to shutdown 

(Fig. 1d, pg. 5)

.

10.  Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching

 

[Trigger EOL Shutdown] 

(Fig. 1e, pg. 5)

.

11.  For Access Control Applications: mount UL Listed tamper switch (Altronix model TS112 or equivalent) at 

 

the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the right 

 side 

(Fig. 5, pg. 7 or Fig. 7, pg. 9)

. Connect tamper switch wiring to the Access Control Panel input or the 

 

appropriate UL Listed reporting device.

Wiring:

Use 18 AWG or larger for all low voltage power connections.

Note:

 Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

 Under normal load conditions, the DC output voltage should be checked for proper 

 

 

 

voltage level eFlow104N: 24VDC nominal rated @ 10A max.

Battery Test:

 

Under normal load conditions check that the battery is fully charged, check specified voltage

 

 

 

(24VDC @ 26.4) both at battery terminal and at the board terminals marked [– BAT +] to 

 

 

 

ensure that there is no break in the battery connection wires.

Note:

 Maximum charging current under discharges is 1.0A.

Note:

 Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.

LED Diagnostics:

Power Supply/Charger

Red (DC)

Green (AC/AC1)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Power Distribution Module

Green (AC)

Power Distribution Module Status

ON

Normal operating condition.

OFF

No Power Output.

Содержание eFlow104N Series

Страница 1: ...t 8 PTC Protected Class 2 Power Limited Outputs eFlow104N16D eFlow104NX16D 10A 24VDC Sixteen 16 PTC Protected Class 2 Power Limited Outputs eFlow104N Series Power Supply Chargers Models Include Rev 10...

Страница 2: ...104NX eFlow104N8 eFlow104NX8 eFlow104N16 and eFlow104NX16 The following units provide Class 2 power limited outputs eFlow104N8D eFlow104NX8D eFlow104N16D and eFlow104NX16D If a power limited output is...

Страница 3: ...60Hz Input Battery Wires Minimum 0 25 spacing must be provided CAUTION Do not touch exposed metal parts Shut branch circuit power before installing or servicing equipment There are no user serviceabl...

Страница 4: ...position Fig 1c pg 5 9 Trigger terminals are end of a line resistor supervised 10k ohms Opening or shorting trigger terminals will cause DC output to shutdown Fig 1d pg 5 10 Place a jumper for non lat...

Страница 5: ...power is present Contact rating 1A 30VDC A removed battery is reported within 5 minutes Battery reconnection is reported within 1 minute power limited Fig 1b pg 5 BAT Stand by battery connections Maxi...

Страница 6: ...Power Limited Outputs N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs From Power Supply Board Factory Install...

Страница 7: ...294 Applications Note 12V batteries are required for UL603 UL1481 and Canadian installations CAUTION Power supply board is factory set for 24VDC Use two 2 12VDC stand by batteries Keep power limited w...

Страница 8: ...employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian ins...

Страница 9: ...minimum 0 25 spacing 12AH Rechargeable batteries are the largest batteries that can fit in this enclosure A UL listed external battery enclosure must be used if using 40AH or 65AH batteries Optional...

Страница 10: ...employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian inst...

Страница 11: ...x 82 6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1...

Страница 12: ...25 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm...

Страница 13: ...ectric w 135o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelect...

Страница 14: ...emote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output...

Страница 15: ...ltronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warra...

Страница 16: ...5AH 6A 10A 1 5A 10A Over 4 Hours 10A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 0A Automatic switch over to stand by battery when AC fails Tran...

Отзывы: