EPC-250 IOI 6-18 All rights reserved © ALTRONIC, LLC 2018
12
7.6
Zero
This user input represents the lower limit of the transducer span.
7.7
Span
This user input represents the higher limit of the transducer span.
7.8
Dec
User input for the amount of decimal places to display
7.9
TRANSDUCER TABLE
When displaying/modifying, it is important to the set the Modbus registers for
the proper data type. For example, if the displayed value is -125 for a signed
integer, it will display as 65410 as an unsigned integer.
TRANSDUCER
SLOPE, X
OFFSET, B
ZERO
SPAN
D.P. CONFIG
COMMENTS
0-50
213
5464
-125
625
1
0-100
213
5464
-250
1250
1
0-300
213
5464
-750
375
1
0-500
213
5464
-1250
6250
0
0-1000
213
5464
-250
1250
0
0-2000
213
5464
-500
2500
0
0-5000
213
5464
-1250
6250
0
VOLTMETER
255
0
0
500
2
0-100.0%, 4-20mA
267
-76
-250
1250
1
dEG1
432
0
0
300
0
dEG2
300
0
-143
675
256
J-TC
271
500
-76
1382
512
K-TC
271
500
-76
1472
768
DIG INPUT N/O
213
5464
-125
625
1025
0 = OK, 1 = FAULT
DIG INPUT N/C
213
5464
-125
625
1281
0 = OK, 1 = FAULT
To display the thermocouples in Celsius, replace the ‘-76’ with ‘-60’ for both
and replace 1382 and 1472 with ‘750’ and ‘800’ respectively. These ranges
should never be changed due to linearization tables.