background image

ALTEC AIR, LLC 

 

P1500W Series Air Dryers User’s Guide 

 

 

Page 67 of 101  

P011787 – Rev. R 

9.11.4  

 

Pull the ring handle on the Safety Relief Valve to release air pressure 

from the air tank. 

 

9.11.5  

 

Verify the Compressor turns on when the tank pressure (

TANK

) falls to: 

 

25.0 PSI* 

for the P1500W, P1500WLP, P1502W, & P1502WLP 

models. *

(50 PSI for Dryers using Firmware v2.84 and older)

 

 

60.0 PSI

  for the P1500WHP & P1502WHP models 

 

9.11.6  

 

Close Front Panel 

If the Compressor Cycling fails either test described, it indicates a problem with 

the Control Board which will need to be replaced.  See sections 11.2 for part 

detail and 11.5 for ordering information.

 

9.12  Testing High Compressor Last Run Time Alarm 

NOTE:

 For this test, allow the Display Screen to cycle through the information 

screens. 

9.12.1  

 

Open Front Panel (section 8.6 )

9.12.2  

 

Start timing when the Compressor turns on. 

9.12.3  

 

Pull the ring handle on the 

Safety Relief Valve (when 

necessary) to keep the Tank 

Pressure (

TANK

) from 

reaching 

90 PSI.

 

This prevents the Compressor 

from shutting down. 

 

When the Compressor runs 

for 3:00 minutes (unless 

adjusted to a different Set 

Point by the user), a High 

Compressor Last Run Time 

Содержание PUREGAS P1500W Series

Страница 1: ...P011787 Rev R P1500W Series Air Dryers User s Guide Models covered P1500W P1500WLP P1500WHP P1502W P1502WLP P1502WHP...

Страница 2: ......

Страница 3: ...2 Introduction PLEASE READ THIS USER S GUIDE THOROUGHLY AND SAVE FOR FUTURE REFERENCE This User s Guide is provided for the benefit of our customers and contains information and direction specific to...

Страница 4: ...rror Bookmark not defined 8 10 Setting the Static PressureError Bookmark not defined 8 11 Setting the Outlet PressureError Bookmark not defined 8 12 Connecting to Common Alarm Terminals Error Bookmark...

Страница 5: ...86 13 6 Can t Create a High Pressure Alarm 86 13 7 Low Outlet Pressure Alarm 87 13 8 Can t Create a Low Pressure Alarm 87 13 9 High Humidity 88 13 10 Can t Create a High Humidity Alarm Shutdown 89 13...

Страница 6: ...you encounter them WARNING For your safety all the information in this User s Guide must be followed to minimize the risk of electrical shock and prevent property damage or personal injury WARNING Ex...

Страница 7: ...MMENDED AND MAY VOID THE WARRANTY IMPORTANT Performing routine maintenance as outlined in the Maintaining Your Dryer section will ensure optimal performance over the lifecycle of your air dryer CAUTIO...

Страница 8: ...nel allowing easier access for adjustment and maintenance and ultra quiet Compressor with an industry leading maintenance interval of 8 000 hours 5 2 Key Features LCD display of all operating paramete...

Страница 9: ...Pa 0 30 7 50 PSI 2 52 7 KPa 2 60 PSI 13 8 103 4 KPa Outlet Air Humidity Less than 2 RH Compressor Type Two cylinder 3 4 HP oil less type Drying Method Heatless Desiccant Operating Temperature Range 40...

Страница 10: ...ture from compressed air 6 Capacity Control Valve Regulates System Pressure and prevents air from bleeding back through the Heatless Dryer 7 Humidity Sensor Measures the Humidity of the compressed air...

Страница 11: ...any procedures WARNING Internal surfaces may be hot Use care when coming into contact with internal components as there is a potential for some of these components to become hot when in operation or s...

Страница 12: ...3 Verify the installation location of the air dryer 6 2 3 1 Well ventilated and free from abrasive dust or chemicals 6 2 3 2 Ambient temperature is between 40 and 85 F optimal NOTE Higher temperatures...

Страница 13: ...de not shown Package located inside the dryer 1 120 VAC Power Cord for P1500W P1500WLP P1500WHP models 1 220 VAC Power Cord for P1502W P1502WLP P1502WHP models 1 Precision Bleed Orifice Fitting 1 User...

Страница 14: ...aterials NOTE If ANY SHIPPING DAMAGE is detected file a claim with the shipping company prior to continuing the installation procedures 6 5 2 Open Front Panel locking latches and remove the Front Pane...

Страница 15: ...se contents package 6 5 5 Remove and discard the packing foam blocks from around the Compressor 6 5 6 Remove the Plug from the Outlet Port by pressing the ferrule down then pulling the plug upward 6 5...

Страница 16: ...011773 section 11 4 6 5 9 Verify that the dryer is powered OFF 6 5 10 Plug AC Power Cord to dryer 6 5 11 Wire or plug the power cord into 110 125 VAC power outlet for P1500W P1500WLP P1500WHP models 2...

Страница 17: ...b until the reading on the pressure gauge is 80 PSI for W WLP 90 PSI for WHP NOTE 90 PSI may be used on W WLP dryers in low flow applications to maintain low humidity 6 5 13 3 Push the knob in to lock...

Страница 18: ...the Outlet Port by pressing the ferrule down then pulling the fitting upward NOTE Save this fitting for use in low flow applications 6 5 17 Connect the air supply line to the Outlet Port NOTE For all...

Страница 19: ...b until the reading on the pressure gauge is 17 PSI for W WLP 60 PSI for WHP 6 5 19 3 Push knob in to lock 6 5 20 Set the Outlet Pressure 6 5 20 1 Pull the Outlet Pressure Regulator knob out or loosen...

Страница 20: ...sten for any hissing sounds which may indicate a fitting or hose air leak With Compressor running 6 5 21 2 Use a 1 inch paint brush to dab soapy water on the air fitting or hose connection to be teste...

Страница 21: ...nts o Well ventilated o Free from abrasive dust or chemicals o Ambient temperature is between 40 and 85 F optimal Shipping foam blocks removed from Compressor System Pressure is set to 80 PSI for W WL...

Страница 22: ...to activate the Limited Warranty on your product Once you register you are eligible to receive free technical support as well as updates concerning your ALTEC AIR products Register Online at www Altec...

Страница 23: ...ituation for potential electrical shock It is highly recommended that you remove all jewelry before performing any procedures WARNING Internal surfaces may be hot Use care when coming into contact wit...

Страница 24: ...isplay When pressed again it will allow the information screens to begin cycling again 8 2 4 Arrow Buttons Used to navigate screens and set values 8 2 5 Display Screen Shows the current dryer readings...

Страница 25: ...ow Air flow out of the system CABINET Temperature of the dryer cabinet compartment 8 2 5 2 Runtime Screen DUTY CYCLE Time Running Time Running Time Off LAST RUN How many minutes the compressor ran dur...

Страница 26: ...bleshooting information 8 2 6 Low Outlet Pressure Alarm Occurs when the Outlet Pressure OUTP drops below the alarm set point for more than one 1 minute Default setting is 6 5 PSI for W models 0 30 PSI...

Страница 27: ...larm is present for three 3 minutes or more the Compressor will SHUTDOWN to protect against damage due to overheating Once the temperature lowers to 112 F the Compressor will re start See section 13 1...

Страница 28: ...ry programmed with a default value Many of can be modified to levels based upon your specific application Network Setup Used to configure network settings including the IP Address Subnet Mask Gateway...

Страница 29: ...Delay default setting is ON 8 4 3 1 Press the Enter Button to access the edit screen 8 4 3 2 Press the Up Down Arrow Buttons to Select the correct choice On or Off 8 4 3 3 Press the Enter Button to s...

Страница 30: ...ress the Up Down Arrow Buttons to Change the value of the selected digit 8 4 5 4 Press the Enter Button to submit the new setting 8 4 5 5 Press the Left Right Arrow Buttons to Select the correct confi...

Страница 31: ...4 8 Press the Up Arrow Button to access the next screen 8 4 9 Reset to Factory Default Values 8 4 9 1 Press the Enter Button to access the reset screen 8 4 9 2 Press the Left Right Arrow Buttons to S...

Страница 32: ...ge 8 4 11 3 Press the Up Down Arrow Buttons to Change the value of the selected digit 8 4 11 4 Press the Enter Button to submit the new setting 8 4 11 5 Press the Left Right Arrow Buttons to Select th...

Страница 33: ...ft Right Arrow Buttons to Select the correct confirmation choice Yes or No 8 4 12 6 Press the Enter Button to confirm the selected choice This will lock in the new setting 8 4 1 Firmware Update 8 4 1...

Страница 34: ...ress the Up and Down Arrow Buttons to Change the value 8 4 2 3 Press the Enter Button to submit the new setting 8 4 2 4 Press the Left Right Arrow Buttons to Select the correct confirmation choice Yes...

Страница 35: ...d lock in the new setting 8 5 Using the Alarm Setup Menu In the Setup Menu 8 5 1 Press the Up Down Arrow Buttons to Select the A in Alarm Setup 8 5 2 Press the Enter Button to access Alarm Setup 8 5 3...

Страница 36: ...n 8 5 5 Set High Outlet Threshold default setting is 20 00 PSI 8 5 5 1 Press the Enter Button to access the edit screen 8 5 5 2 Press the Left Right Arrow Buttons to Select the digit to change 8 5 5 3...

Страница 37: ...to change 8 5 7 3 Press the Up Down Arrow Buttons to Change the value of the selected digit 8 5 7 4 Press the Enter Button when to submit the new setting 8 5 7 5 Press the Left Right Arrow Buttons to...

Страница 38: ...r Button to confirm the selected choice This will lock in the new setting 8 5 10 Press the Up Arrow Button to access the next screen 8 5 11 Set High Duty Cycle default setting is 70 8 5 11 1 Press the...

Страница 39: ...Button to access Network Setup 8 5 14 Enter Keyword default Keyword is 123456 8 5 14 1 Press the Left Right Arrow Buttons to Select the digit to change 8 5 14 2 Press the Up Down Arrow Buttons to Cha...

Страница 40: ...ubmit the new setting 8 5 15 5 Press the Left Right Arrow Buttons to Select the correct confirmation choice Yes or No 8 5 15 6 Press the Enter Button to confirm the selected choice This will lock in t...

Страница 41: ...the selected choice This will lock in the new setting 8 5 17 Set Gateway Address default is 000 000 000 000 8 5 17 1 Press the Enter Button to access the edit screen 8 5 17 2 Press the Left Right Arr...

Страница 42: ...ss the edit screen 8 5 18 2 Press the Left Right Arrow Buttons to Select the digit to change 8 5 18 3 Press the Up Down Arrow Buttons to Change the value of the selected digit 8 5 18 4 Press the Enter...

Страница 43: ...e Up Down Arrow Buttons to Change the value of the selected digit 8 5 19 4 Press the Enter Button when to submit the new setting 8 5 19 5 Press the Left Right Arrow Buttons to Select the correct confi...

Страница 44: ...e new setting 8 5 20 4 Press the Left Right Arrow Buttons to Select the correct confirmation choice Yes or No 8 5 20 5 Press the Enter Button to confirm the selected choice This will lock in the new s...

Страница 45: ...released 8 7 3 To prevent pressure from building back up power the dryer OFF See section Error Reference source not found for detail 8 7 4 Close Front Panel 8 8 Connecting to Common Alarm Terminals 8...

Страница 46: ...for OPEN ON ALARM operation 8 9 4 Close Panel 8 10 Connecting via Web Browser If the Air Dryer IS connected to an IP network The Air Dryer must be configured with a valid IP Address Subnet Mask and Ga...

Страница 47: ...Web Browser 8 10 1 Type the IP Address of the P1500W Series air Dryer in the Address text box of the web browser The Web Browser connection offers five 5 screens to the user Status Screen Displays th...

Страница 48: ...1 P011787 Rev R 8 11 Using the Status Screen Displays the readings and alarms monitored in the P1500W Series Air Dryer Provides remote ALARM RESET Readings are displayed in BLACK unless an alarm is pr...

Страница 49: ...tus will display Alarm if any alarms are present Keyword validation is required for ALARM RESET and RESET TOTAL RUN TIME 8 11 1 Resetting an Alarm 8 11 1 1 Click on the ALARM RESET Button to remotely...

Страница 50: ...01 P011787 Rev R 8 11 1 3 Click on SUBMIT Button when done 8 11 2 Resetting Compressor Total Run Time 8 11 2 1 Click on the RESET TOTAL RUN TIME Button to remotely reset Compressor Total Run Time disp...

Страница 51: ...de Page 51 of 101 P011787 Rev R 8 11 2 3 Click on SUBMIT Button when done 8 12 Using the Config Screen All configuration of Set Points Setups and Keyword can be made in this screen NOTE Reference Appe...

Страница 52: ...to change values The CHANGE KEYWORD Button allows you to configure a new Keyword Keyword validation is required for the following o Changing a Set Point value o Changing the Keyword 8 13 Using the Eve...

Страница 53: ...ALTEC AIR LLC P1500W Series Air Dryers User s Guide Page 53 of 101 P011787 Rev R 8 14 Using the Firmware Screen Displays the current firmware version and date of the P1500W Series Air Dryers...

Страница 54: ...validation is required to update firmware 8 15 Connecting via SNMP Using SNMP to connect and communicate with the P1500W Series Air Dryer is dependent upon the specific SNMP Management software used o...

Страница 55: ...s air dryer require the equipment to be running creating a situation for potential electrical shock It is highly recommended that you remove all jewelry before performing any procedures WARNING Intern...

Страница 56: ...5 coming directly from the Compressor 9 2 3 Use an Amp Meter to measure the running amps With the Compressor running the running amps should measure 6 3 amps or below for the P1500W P1500WLP P1500WHP...

Страница 57: ...Panel section 8 6 9 3 3 Depressurize the air dryer section 8 7 9 3 4 Locate wire 5 at the solid state relay and wire 6 on Control Board 9 3 5 Lift plastic cover on Control Board over wire 6 9 3 6 Pow...

Страница 58: ...cate the Incoming POWER connector inside the dryer 9 4 3 Use a Voltmeter to measure the voltage inside dryer 9 4 3 1 Place the probes between the Power Connector and terminal insulation so that they t...

Страница 59: ...ing the power to the recommended level of voltage 9 5 Measuring Voltages at Solid State Relay 9 5 1 Open Front Panel section 8 6 9 5 2 Locate the Solid State Relay inside the dryer at the top of back...

Страница 60: ...e P1502W P1502WLP P1502WHP models 9 5 6 Use a Voltmeter to measure across the DC terminals Should measure 0 VDC 9 5 7 Close Front Panel If any of the AC voltage measurements are different than indicat...

Страница 61: ...el section 8 6 9 6 2 Place a piece of insulating material over the Compressor for this test i e piece of cardboard 9 6 3 Locate the heatless dryer purge solenoids inside the air dryer WARNING Internal...

Страница 62: ...for purging air Air should Purge from Tower 1 side Purge from Tower 2 side 30 Seconds later Purge from Tower 1 side 30 Seconds later and so on 9 6 5 Remove insulating material from top of the Compress...

Страница 63: ...h a 9 16 wrench disconnect hose from the Unloader Valve 9 7 4 Place your hand under the Unloader Valve to verify for air flow The Unloader Valve should purge all the head pressure when the Compressor...

Страница 64: ...ing 9 8 1 Open Front Panel section 8 6 9 8 2 Locate the Heatless Dryer Cycle Timer The timer has three 3 sets of terminals from left to right VALVE Left solenoid IN Incoming power VALVE Right solenoid...

Страница 65: ...ove 90 F 9 9 1 Place your hand outside the dryer to feel for air being blown outwards NOTE The fan will turn OFF when the cabinet temperature is below 80 F If the fan is not blowing air outwards as de...

Страница 66: ...ribed it must be replaced See sections 11 2 for part detail and 11 5 for ordering information 9 11 Testing Compressor ON OFF Cycling 9 11 1 Open Front Panel section 8 6 9 11 2 When the Unit Screen 8 2...

Страница 67: ...escribed it indicates a problem with the Control Board which will need to be replaced See sections 11 2 for part detail and 11 5 for ordering information 9 12 Testing High Compressor Last Run Time Ala...

Страница 68: ...se Front Panel If you are unable to create a High Compressor Last Run Time LAST RUN alarm as described see section 13 18 for troubleshooting information 9 13 Testing Humidity Alarm and System Shutdown...

Страница 69: ...dryer ON 9 13 6 Allow the Humidity reading to rise over 10 0 After three 3 minutes verify that a Humidity Alarm appears and the dryer goes into SHUTDOWN mode 9 13 7 Replace the Humidity Sensor into t...

Страница 70: ...4 1 Make a note of the current Outlet Pressure OUTP reading 9 14 2 Open Front Panel section 8 6 9 14 3 Pull the Outlet Pressure Regulator knob out or loosen the retaining nut LP Models 9 14 4 Turn kno...

Страница 71: ...to lock or tighten the retaining nut LP Models 9 14 7 Press the RESET Button 9 14 8 Close Front Panel If you are unable to create a High Outlet Pressure Alarm as described see section 13 6 for troubl...

Страница 72: ...P P1502WHP models After one 1 minute the Low Pressure Alarm should appear on the display 9 15 5 Turn Outlet Pressure Regulator knob clockwise until Outlet Pressure OUTP reading rises to the reading re...

Страница 73: ...IDITY SENSOR FITTING DAMAGE TO THE SENSOR MAY OCCUR With Compressor NOT running 9 16 1 Listen for any hissing sounds which may indicate a fitting or hose air leak With Compressor running 9 16 2 Use a...

Страница 74: ...aintenance section 10 3 log sheets and record all completed maintenance for historical tracking and reference purposes The log sheets include a Section reference column which indicates the User s Guid...

Страница 75: ...tion or standby IMPORTANT Performing procedures not described in this User s Guide or installing components not supplied by ALTEC AIR is NOT RECOMMENDED AND MAY VOID THE WARRANTY IMPORTANT Performing...

Страница 76: ...Flow Rate FLOW Error Reference source not found Measure Record Compressor Amp Draw 9 2 Measure Record Incoming Voltage 110 125 VAC for P1500W P1500WLP P1500WHP models 208 230 VAC for P1502W P1502WLP P...

Страница 77: ...Visually Inspect Inside Outside of Unit for Loose Wiring or Hardware Maintenance Performed by Date of Maintenance NOTE COPY OR PRINT THIS PAGE AND KEEP IT WITH THE AIR DRYER 10 3 8 000 Hour Maintenanc...

Страница 78: ...models 60 PSI for P1500WHP P1502WHP models Error Reference source not found Set Outlet Pressure Error Reference source not found Test Consistent Heatless Dryer Cycling 9 6 Test Compressor ON OFF Cycli...

Страница 79: ...men d Spare Precision Bleed Orifice Fitting P013349 1 Power Switch M038428 1 Fan P40801 1 Static Pressure Regulator W WLP models WHP models P010279 P010622 1 Air Tank 1 Solid State Relay P05992 1 1 St...

Страница 80: ...lator W models WLP models WHP models P010279 P012316 P010622 1 Flow Block 1 Unloader Valve P1500W Series 110 VAC P1502W Series 220 VAC P011022 P010453 1 Safety Relief Valve P011777 1 Control Board P01...

Страница 81: ...Parts Description Part Number Quantity Recommend Spare Heatless Dryer P1500W Series 110 VAC P1502W Series 220 VAC PHF2C106023 PHF2C20623 1 Desiccant Chamber P2004036 2 Cycle Timer P1500W Series 110 V...

Страница 82: ...ake filter Compressor muffler P011910 2 8 000 Hour Maintenance Kit Includes heatless dryer maintenance kit and Compressor maintenance kit P012252 1 Universal Rack Mounting Kit Includes mounting bracke...

Страница 83: ...ponents goes beyond the scope of this User s Guide and will not be covered Please refer to the information included with the specific replacement part for this instruction Once you have identified you...

Страница 84: ...d o Replace desiccant o rings check valves springs and complete solenoid assembly o Test proper component operation Desiccant Tower Repack o Clean out tower and replace desiccant filter and o ring Cir...

Страница 85: ...ection begins with the most likely cause s of the issue Otherwise they start from the simplest possibilities and progress to more complicated ones This troubleshooting guide is designed to be easy to...

Страница 86: ...ing installation operation testing and maintenance of this air dryer require the equipment to be running creating a situation for potential electrical shock It is highly recommended that you remove al...

Страница 87: ...ify High Outlet Pressure Alarm set point section Error Reference source not found Raise High Outlet Pressure Alarm set point section Error Reference source not found 13 6 Can t Create a High Pressure...

Страница 88: ...t section Error Reference source not found Lower the Low Outlet Pressure Alarm set point section Error Reference source not found Leak in the air system With no outlet flow test fittings and hoses for...

Страница 89: ...e Verify Flow Rate FLOW reading is low section Error Reference source not found Install the included Precision Bleed Orifice fitting to maintain a constant air flow section Error Reference source not...

Страница 90: ...arm Shutdown These troubleshooting steps assume that the Humidity Element is removed from the Humidity Block during the Testing Humidity Alarm and System Shutdown section 9 13 procedures Possible Caus...

Страница 91: ...Recommended ambient temperature is 40 85 F Lower the ambient temperature of the dryer s operating location 13 13 Inconsistent Heatless Dryer Cycling Possible Cause Check Corrective Action Defective So...

Страница 92: ...tion 9 5 If measurements are incorrect replace Control Board section 11 2 13 15 Compressor Won t Build Pressure Possible Cause Check Corrective Action Low System Pressure Verify System Pressure sectio...

Страница 93: ...ion 11 2 or send it in for repair section 12 13 17 High Compressor Last Run Time Alarm Possible Cause Check Corrective Action Low System Pressure Verify System Pressure section Error Reference source...

Страница 94: ...e Alarm Set Point section Error Reference source not found Allow the Compressor to run longer than the verified set point section 9 12 Defective Control Board Verify that the Compressor has run longer...

Страница 95: ...lems and solutions covered in the Troubleshooting Your Dryer section and you still require further assistance to correct a problem contact ALTEC AIR Technical Support 800 521 5351 option 1 Have the fo...

Страница 96: ...ALTEC AIR LLC P1500W Series Air Dryers User s Guide Page 96 of 101 P011787 Rev R 14 2 Set Point Limits and Defaults 14 2 1 System Adjustments...

Страница 97: ...essor Last Run Time Alarm 2 00 5 00 3 00 Minutes High Cabinet Temperature Alarm 120 Deg F YES Compressor Total Run Time Alarm 8000 Hours 14 2 3 System Operations Description ON Value OFF Value Default...

Страница 98: ...t Run Time Reading Numeric Seconds System Status ON SHUTDOWN Compressor Status ON OFF Fan Status ON OFF Heater Status Outdoor Unit Only ON OFF Alarm Readings Read Only High Flow Alarm OK Alarm High Ou...

Страница 99: ...the user in turn should file any damage claim against the carrier All warranty items are F O B Broomfield Colorado Freight charges are the responsibility of the user This warranty shall not apply to a...

Страница 100: ...Colorado 80020 800 521 5351 303 427 3700 Fax 303 657 2233 info AltecAIR com www AltecAIR com 16 2 Sales 800 521 5351 option 2 Fax 303 657 2205 sales AltecAIR com parts AltecAIR com 16 3 Service 800 52...

Страница 101: ...___________________________________ ________________________________________________________________________ ________________________________________________________________________ __________________...

Отзывы: