Page 27 of 101
P011787 – Rev. R
(Default setting is 10.0%)
If this alarm is present for one (1) minute or more, the air Dryer will go into
SHUTDOWN
mode to prevent saturated air from being delivered to the
supply line.
See section 13.9 for troubleshooting information.
8.2.9
High Cabinet Temperature Alarm -
Occurs when the temperature in
the cabinet rises above 120°F for
more than ten (10) seconds.
If this alarm is present for three (3) minutes or more, the Compressor will
SHUTDOWN
to protect against damage due to overheating. Once the
temperature lowers to 112°F the Compressor will re-start.
See section 13.12 for troubleshooting information.
8.2.10
High Compressor Last Run Time Alarm –
Occurs when the compressor
takes longer to pressurize the
air tank than the set point for
the alarm. (Default setting is
3:00 minutes)
See section 13.17 for troubleshooting information.
8.2.11
Compressor Total Hour Alarm –
Occurs when the compressor
has reached an 8,000 hour
maintenance interval. Perform
the required maintenance.
See section 10.3 for maintenance information.