0370260-J0 Rev B
5.2.
Single String Display (with optional battery sensors)
The Single String Display lists all jars associated with a string. Each string can be given its own name which is displayed
near the top of the page.
This page will display two, three or four jars for strings. For each jar present in the string the jar voltage and
admittance is displayed.
The button face on this page is color-coded to indicate the jar status. Normal status is indicated by gray, red indicates a
major alarm, yellow indicates a minor alarm, green indicates an admittance measurement is in process on the jar and
magenta indicates a warning condition.
Press a
Jar
button to view the detailed information on the jar.
The
Discharge Status
is displayed. Pressing the
A
button allows configuration of the alarm status for this parameter.
The
String Status
field displays the present string monitoring status which is a summary of the sensor status as
described below.
String Status
Description
Normal
The status of all sensors on this string are normal.
Disabled
The string is disabled through SNMP.
Shorted
The RBMS Plus output is shorted somewhere in the sensor daisy chain.
MissingSensors
More sensors were expected.
TooManySensors
More sensors are present than the string can handle.
SensorFault
One or more sensors are not communicating.
Alarms
One or more sensors have alarms.
Initializing
The string is initializing.
SensorDisabled
One or more sensors are disabled through SNMP.
StringDisconnected
Nothing is connected to the RBMS Plus string port.
NoSensorCom
Something is connected to the port, but no sensors are communicating.