proCeed as follows for the
LWC 120
:
If unit is closed, open bottom front panel…
“Transport with a hand truck”
loosen the quick-release screws for the lower front
panel (= control side), remove lower front panel and
set aside…
Rinse and fill unit via the filling and emptying valve…
CautIon.
Do not exceed a pressure of 2.5 bar when
rinsing the unit. the drain line of the
heating circuit safety valve must be closed
before rinsing and filling.
notICe.
rinse heat pump and heating circuit for
about 5 minutes.
lWc 120
1 filling and emptying valve
during this process, turn the lever of the switching
valve used for the hot water circuit counter-
clockwise. press the reset button and rinse for
approx. 1 minute…
1 switching valve
1 Reset button
2 move the lever on the top of the
switching valve from right to top
After completion of this procedure move the
lever of the switching valve for the hot water
circuit clockwise to the starting position.
To do so, press the reset button…
1 Reset button
2 move the lever on the top of the
switching valve from top to right
bleed the heating circuit and hot water circuit…
lWc 120
1 bleed valve